Interlogix ATS1744 Installationsanleitung
Interlogix ATS1744 Installationsanleitung

Interlogix ATS1744 Installationsanleitung

Vierfach datenbus entkoppler

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ATS1744 Quadruple Databus Isolator Installation
Sheet
EN DE
IT
F2
F1
S1
J12
J2
+12V 0V
D+ D-
COMMS Slave 1
EN: Installation Sheet
Description
The ATS1744 quadruple databus isolator is a functional
isolator for the ATS databus. It can isolate 4 ATS-slave loops.
In principle, each loop supports all peripherals in one area,
which means that the isolator can isolate 4 areas.
Shorts or open in one or more slave loops will not interrupt the
other slave loops and the master loop.
Mounting the unit
Mount the ATS1744 PCB in any existing ATS control panel
enclosure that supports the BB format.
Connections
J1 COMMS of master loop
+12 / 0V: 12 VDC supply input. 39 mA max with no other
peripheral devices connected.
D+ / D−: Positive and negative data connection of the RS485
databus.
J2 to J5 COMMS of slave loop
+12 / 0V: 12 VDC supply output. 300 mA max.
D+ / D−: Positive and negative data connection of the RS485
databus. Units can be up to 1.5 km from the 4-door DGP or
control panel, depending on the cable used. Recommended:
WCAT52/54; 2-pair twisted, shielded, data cable.
© 2019 UTC Fire & Security Americas Corporation, Inc.
F4
F3
S2
J3
TERM
+12V 0V
D+ D-
COMMS Slave 2
Rx Tx
TERM
Master
S3
+12V 0V
COMMS Slave 3
J12 earth connector
Connect the shield of the ATS COMMS cable. Ensure that the
shielding of one cable must be connected to one system earth.
See the Advisor Master Installation Guide.
Fuse connections
F1 to Comm. Slave 1
F2 to Comm. Slave 2
F3 to Comm. Slave 3
F4 to Comm. Slave 4
Note:
All fuses F1 to F2: 315 mA, fast 20x5.
LEDs
Rx: LED (yellow) flashes to indicate polling data is being
received on the system databus from the ATS control panel. If
the LED does not flash, the control panel is not operational or
the databus is faulty (usually cabling).
Tx: LED (red) flashes to indicate that any DGP or RAS is
replying to polling from the ATS control panel. If the Rx LED
flashes but the Tx LED does not, it indicates that the DGP is
not programmed to be polled in the control panel or that it is
addressed incorrectly or any of the databus is faulty.
Sy: LED (red) flashes to indicate that any DGP or RAS
connected to Slave y (1 to 4) are replying to polling from the
ATS control panel. If the Sy LED is off, the slave loop is
shorted.
Links
TERM: System databus term link. Refer to Advisor Master
Installation Guide.
1 / 4
J1
S4
J4
J5
D+ D-
TERM
+12V 0V
D+ D-
COMMS Slave 4
P/N 1077857 (ML) • REV B • ISS 14JUN19

Werbung

loading

Inhaltszusammenfassung für Interlogix ATS1744

  • Seite 1 Mounting the unit Note: All fuses F1 to F2: 315 mA, fast 20x5. Mount the ATS1744 PCB in any existing ATS control panel LEDs enclosure that supports the BB format. Rx: LED (yellow) flashes to indicate polling data is being Connections received on the system databus from the ATS control panel.
  • Seite 2 Contact information system www.utcfireandsecurity.com or www.interlogix.com In a full system you can connect more ATS1744 isolators. For customer support, see www.utcfssecurityproducts.eu A control panel, which controls 16 areas, will most probably have 4 isolators. However all slave loops are fused with 315 mA.
  • Seite 3 IT: Istruzioni d’installazione VdS-Anerkennung Klasse C beantragt Rechtliche Hinweise Descrizione L'ATS1744 è un modulo attivo che ha la funzione di ripartire e Hersteller INVERKEHRBRINGER: UTC Fire & Security Americas Corporation, Inc. isolare il bus dati ATS. ATS1744 divide il bus principale in 3211 Progress Drive, Lincolnton, NC, 28092, USA 4 loop avendo così...
  • Seite 4 In un sistema completo, potrebbero essere connessi più consegnarli presso i centri di raccolta preposti. moduli ATS1744. In una centrale che controlla 16 aree, si Per maggiori informazioni vedere: avranno probabilmente 4 isolatori, dove ogni loop è protetto www.recyclethis.info...