360° SPOT TYPE MOTION SENSOR
USAGE AREAS
• At the building entrances, stair vestibutes.
• At the long halls within the flats.
• At the places required within the flats.
• At covered parking lots.
• At the requisite locations within the hotels.
• At the schools, hospital and oil filing station.
"OFFERS ENERGY SAVING FEATURE''
GENERAL SECURITY CAUTIONS
• Take off the original package and control if there is any damage of transportation and general
view of the product.
• Do not use the product at cross purposes.
• Keep it away from water and moist areas.
• Do not use the product at dusty, dirty and rusty places.
• Do not supply high voltage.
• Do not apply any liquid.
• Protect from any stroke.
• Using ~230-240V voltage is so dangerous that only the specialist electricians must install
and apply.
CAUTIONS FOR INSTALLATION AND USAGE
• Installing must be carried out professionally in accordance with applicable national wiring and
electrical operating conditions.
• Turn of the network before mounting.
• Do not mount the product near the radiator and moist areas.
• Place the product horizontal to the ceiling.
• Fix the bulbs before operating.
• Use 10A fuse the supply input.
• Factory setting; daylight adjustment is at darkness, time adjustment is at the shortest.
• Setting can be made 10 - 15 second after the releasing of the power.
• Time and daylight setting can be made during the day or night.
• Do not change the time and daylight settings abruptly.
• Do not make a second adjustment before you get a result from the first setting of the time
and daylight.
• After you determine the right setting of the daylight, you can arrange the time as you need.
• The best result for the daylight setting can be obtained by adjusting the minimum. And that
you can find the correct setting for sensitivity incrementally.
• When a cleaning needed for the product, take of carefully and clean with a dry rag.
• Avoid mounting the detector close to objects that can cause rapid temperature changes such
as heaters, fans, refrigerators and ovents etc, and prevent the detector from point-blank
sunshine.
• It can cause the device operate inaccurately if there is tree, brushes etc. in the coverage area.
• The device has Y type connection.
• 10365 product is suitable for incandescent lamp, Led lamp&light and fluorescent lamp which
has electronics ballast or mechanic ballast with starter .

SPECIFICATIONS

Operating voltage
~230-240VAC / 50 Hz
Angle of coverage
360°
Height
2.8 m.
Width
9 m.
Time setting
10 sec. ± 1 sec. / 6 min. ± 10 sec.
Lighting load
Max 1000W incandescent
Max 400W fluorescent
Protection class
IP54
Class II
Opr. temperature
-20 °C ~ +40°C
Power consumption
1.5W
Mounting section size
Ø 70 mm
Detection range is determined at the temperature of +20°C
SETTING
(c)
(c) Time setting
Light ON time can be adjusted continuously from "10 sec. / 6 min." If you turn the knob
counterclockwise device will operate at minimum time. (10 seconds)
Control dial set to - = Shortest time (10 sec. ± 1 sec.)
Control dial set to + = Longest time (6 min. ± 10 sec.)
(d) Daylight setting
The sensor's response threshold can be infinitely varied from 2-2000 lux.
If you turn the knob counterclockwise device will operate at dark.
Control dial set + = daylight operation approx. 2000 lux.
Control dial set - = night-time operation approx. 2 lux.
NOTE: Device will automatically make its own offset by checking environment for approximately
5 minutes after the first installation. After this period device will operate normally. If you think
the device does not operate normal in first installation, please wait for 5 minutes and start to
test again. Be sure that there is no motion by this period.
10365
10365
(d)
Mounting
After placing the long parts of the both springs inside the slot and short parts of the both
springs out of the slot on the ceiling as shown on the Figure (a), press the product through the
slot and make the springs tense as shown on the figure (b). Thus, installation is achieved
successfully.
Detection area
Adjustable 30° - 360° by the angle apparatus

TROUBLESHOOTING

MALFUNCTION
• Lamp is off
• There is no
electricity on the
device
• Continuously
lamp is on
• Change perception
area in device
DETECTION AREA
Detection area of motion sensors depends on the angle between PIR detector and moving
direction, temperature , mounting style and mounting place. Temperature is very important for
operation for motion sensor like all electronic devices. Using higher value of loads written on
manuals and packages will decrease temprature inside the device when using Na-De Motion
Sensor. As a result detection range will decrease and may cause defect of electronic components.
Environment temperature will also cause decrease of detection range. Detection range give is
determined at +20°C. If the weather is hot, it will decrease.
Walking targential to the sensor
(normal detection range)
The maximum detection range can be realized when walking tangential to the sensor (figure1)
When walking directly to the sensor detection range will be low. Because you will not be able
to cut vertical areas. Detection range of 10365 model is 9 m as diameter and 4,5 m as radius.
GUARANTY
We will remedy defects caused by material flaws or manufacturing faults. The warranty will be
met by repair or replacement at our own discretion. The warranty shall not cover damage to
wear parts, damage or defects caused by improper treatment or maintenance. Further
consequential damage to other object is excluded.
Claims under the warranty will only be accepted if the unit is sent fully assembled and well
packed complete with a brief description of the fault, a receipt or invoice ( date of purchase
and dealer's stamp) to the appropriate Service Center.
info@na-de.com.tr • ww.na-de.com.tr
(a)
L1
L
Lamp
N
30° right to movable sensor
CAUSE
• Daylight adjustment set to
• Control daylight setting and
night-time mode during daytime
re-adjust
operate
• Fit the bulp into the lamp holder,
• Bulb faulty or there is no
if it still does not operate, change
connection
the bulb.
• Power switch off or no electricity
• Check the electricity and power
on.
• Fuse faulty
• Change the fuse.
• Fuse switch off or fuse faulty
• Check the fuse if necessary use
a new fuse.
• Connection faulty.
• Check the connection cables.
• Continuously movement in
• Check the detection zone.
detection zone
• Cars on the streets are being
• Avert it is being detection.
detected.
• Wind, rain, snow is moving to the
• Change detection zone, change
trees & bushes or open windows in
site of installation.
detection zone.
• Sudden temperature changes due
• Change site of installation or
to weather(wind, rain, snow) or the
keep the reasons away.
air expelled from fans.
• Different ambient temperatures.
• Change site of installation.
Figure 1
Walking directly to the sensor
(lower detection range)
GB
(b)
4.5m.
4.5m.
9 m.
SOLUTION