Oxygen Automation strongly suggests to install mechanical stops, both in opening and in closing, for an accurate and reliable installation in time.
The Hydra control unit works with working times and adds a few seconds automatically to always guarantee total opening and closing in all conditions (bad
weather, strong wind, snow and rust). If you do not have mechanical stops, you must enable the slowdowns (DIP6 = ON)
1) Make two jumpers between 11 - 17 and 11-18 and set DIP n. 4, 9, 10, 11, 12 to ON so that all safety devices (factory) are excluded 7 LEDs on
2) Check that the capacitors are connected between the black and brown cables of each motor (in parallel).
The colors of the cables are: Grey = common, Brown and Black = opening and closing
3) To save the remote controls:
- You can save the remote controls only if the gate is closed.
- Leave DIP2 = OFF (factory)
- Switch on the card with the 230V and wait for the gate to close automatically (if it opens, invert the brown and black of the motors) If it stays still, it means that
it is already closed
- With the gate closed, press and release button P1, the LED lights up
- Press a button on the remote control, the LED flashes
- Wait 10 seconds until the LED goes out = Remote control programmed
If this procedure does not work, perform the RESET memory procedure and repeat it.
4) Follow the "Time setting" procedure step by step, with one or two doors depending on your kit. Do not press the P1 button in case of 2 doors.
5) connect the external photocells as shown in figure 2 (If it has two pairs of photocells, the two contacts of the receivers must be connected in series)
Remove the jumper between 11 and 18. Do not remove the jumper 11 -17.
6) Optional, connect the external light as shown in figure 1 (to activate the flashing)
7) Adjust the force, as indicated in the relevant chapter. A correct setting is between 3 and 5 flashes for electro-mechanical motors.
8) Oxygen Automation's Technical Service is available in any case: service@oxygenautomation.com
CONNECTIONS
N.
CLAMPS
1 - 2
230V LIVE AND NEUTRAL
3
MOTOR 1 OPENING
4
MOTOR 1 COMMON
5
MOTOR 1 CLOSING
6
MOTOR 2 OPENING
7
MOTOR 2 COMMON
8
MOTOR 2 CLOSING
9 – 10
FIXED LAMP
11
ACCESSORIES COMMON
12
NC OPEN LIMIT SWITCH M1
13
NC CLOSE LIMIT SWITCH M1
14
NC OPEN LIMIT SWITCH M2
15
NC CLOSE LIMIT SWITCH M2
16
NO START
17
NC STOP
18
NC CLOSING PHOTOCELLS
19
NO PEDESTRIAN START
20
NC OPENING PHOTOCELLS
21
24VAC ACCESSORIES
22
0 VAC ACCESSORIES + LOCK
23
12 VAC ELECTRIC LOCK
24
ANTENNA COMMON
25
ANTENNA INPUT
26 - 27
FLASHING LAMP CONTACT
TWO WINGS GATE SETTING (TWO MOTORS)
- Gate Closed
- Set Dip Switch N.1 = On
- Press Remote Control Button - First wing opens
- Wait for wing displacement (we suggest 2 Or 3 seconds)
- Press Remote Control Button - Second wing opens
- First wing is opened - Wait for 1 or 2 seconds - Press Remote Control Button to stop it
- Second wing is opened – Wait for 1 or 2 seconds - Press Remote Control Button to
stop it
- Wait for desired pause time in opening (normally between 10 and 30 seconds)
- Press Remote Control Button - Second wing closes
- Wait for wing displacement (we suggest 2 or 3 seconds)
- Press Remote Control Button - First wing closes
- Second wing is closed - Wait for 1 or 2 seconds - Press Remote Control Button to stop
it
- First wing is closed - Wait for 1 or 2 seconds - Press Remote Control Button to stop it
- Set Dip Switch N.1 = Off
PEDESTRIAN GATE SETTING
- Gate Closed
- Set Dip Switch N.1 = On
- Press Pedestrian Remote Control Button – First wing opens
- Wait for desired opening angle - Press Pedestrian Remote Control Button to stop it
- Wait for desired pause time in opening (normally between 5 and 10 seconds)
- Press Pedestrian Remote Control Button - Wing closes
- Wing is closed - Wait for 1 or 2 seconds - Press Remote Control Button to stop it
- Set Dip Switch N.1 = Off

QUICK SETUP

DIP SWITCH SETTING
DIP
ON
1
TIME SETTING MODE
STANDARD MODE
2
STEP BY STEP MODE
RESIDENTIAL MODE
3
CONDOMINIUM ON
CONDOMINIUM OFF
4
DISABLE INPUT 20
ENABLE INPUT 20
5
ELECTRIC LOCK ON
ELECTRIC LOCK OFF
6
SLOWDOWN ON
SLOWDOWN OFF
7
+3 MIN. LAMP OFF
+3 MIN. LAMP ON
8
HYDRAULIC MOTORS
MECHANIC MOTORS
9
DISABLE INPUT 12
ENABLE INPUT 12
10
DISABLE INPUT 13
ENABLE INPUT 13
11
DISABLE INPUT 14
ENABLE INPUT 14
12
DISABLE INPUT 15
ENABLE INPUT 15
- Step-by-step = automatic closing disabled
- Residential = step-by-step with automatic closing -
Condominium = does not accept other STARTs during
opening
*Hydraulic Motor Settings: DIP 8 = ON and DIP 6 =
OFF
GATE TIME SETTINGS
FURTHER SETTINGS
ENGLISH
OFF
REMOTE CONTROLS STORE
Press and release button P1, LED automatically lights up
- Press a button on the remote control, the LED flashes, Remote control
saved
-As long as the LED is on, additional remote controls can be added.
- Wait 10 seconds until the LED turns off automatically.
*You can save remote controls only if the gate is closed: Set DIP2=OFF, switch-
on main power supply and wait for the gate to close automatically.
PEDESTRIAN REMOTE CONTROL BUTTON STORE
- Press and release button P1 twice, the LED automatically lights up
solidly, flashes and lights up solidly again
- Press another button on the remote control, the LED flashes, Remote
control saved, as long as the LED is on you can add additional remote
controls
-Wait about 10 seconds until the LED turns off automatically
MEMORY RESET
Press and hold button P1, LED automatically lights up solidly
- Press and hold P1 until the LED goes out.
- Release P1, LED flashes, Memory is empty
SINGLE WING GATE SETTING (ONE MOTOR)
- Gate Closed
- Set Dip Switch N.1 = On
Press P1 Button on the control unit - Wing opens
- Wing is opened - Wait for 1 or 2 seconds - Press Remote Control Button to stop it
- Wait for desired pause time in opening (normally between 10 And 30 Seconds)
- Press Remote Control Button - Wing closes
- Wing is closed - Wait for 1 or 2 seconds - Press Remote Control Button to stop it
- Set Dip Switch N.1 = Off
FORCE ADJUSTMENT
- Gate closed
- Press Remote Control Button – First wing
opens
- During the opening Press P1 Button to
decrease the force of 10% (up to 6 levels)
- Switch off 230v main power
- Switch on 230v main power, Prog Led
automatically flashes, between 7 and 1 (7=Max
1=Min)
*If Set Dip 8 to on = Max force (7 flashes)
*fast closing function : during pause the gate closes 3 seconds after having released the photocells
REMOTE CONTROL (KEY FOBS)
FAST CLOSING*
- During gate time setting, during
desired pause time (gate is fully
opened and stopped)
- Activate photocells for 2-3
seconds – Prog Led flashes – fast
closing is activated

Werbung