Operating Instruction
Device operation
1. Switch on the gas warning unit using the
slide switch - move the slide switch to the
left, all the LEDs light up, a short perma-
nent acoustic signal is sounded and the
heat-up phase of approx. 25 s begins, -
then the green
a ticking noise indicates that the device is
ready for operation.
2. If escaping gas is detected, the acoustic
signal (ticking noise) becomes faster as
the concentration increases.
3. When the 1st switching threshold of 100
ppm has been exceeded, the yellow LED
lights up.
4. When the 2nd switching threshold of - 1
Vol% has been exceeded, the red LED
lights up. - The permanent acou-
stic signal can be heard.
On account of its function, the gas detec-
tor gas warning unit must not be used as a
measuring device or for personal protection!
Calibrating the device
Re-calibration of the 2nd switching threshold:
1. Switch the device on, wait until the heat-
up phase is over.
2. Apply testing gas 1 Vol% methane to the
diffusion head, keep the testing gas flow
to a minimum during the calibration pro-
cess.
3. Use a screwdriver to set the potentiome-
ter in such a way that the red LED lights
up and the permanent signal can be
heard.
4. End of calibration process.
www.herthundbuss.com
Charging the NiMH batteries
1. Switch the gas warning unit off, exert
LED lights up and
2. Battery charting time: 12...24 hours.
3. When replacing the batteries, make sure
4. Close the housing again by clicking the
5. The charging procedure should take place
6. More than 500 charging and discharging
7. Only charge the batteries in the device
8. Long-term storage or excessively long
Calibration data
All gas warning unit devices have been pre-
calibrated in the factory for the following
measuring levels:
Methane: Yellow LED - 100 ppm
Propane: Yellow LED - 100 ppm
slight pressure to release the compart-
ment cover on the bottom of the device
and open it forwards, remove the NiMH
batteries.
of correct polarity.
compartment cover into place on the top
of the device, and locking it by exerting
slight pressure.
in the temperature range of 0...45°C.
cycles can be expected.
through the charging socket when the de-
vice is switched off!
battery charging leads to a reduced cell
capacity. This loss of capacity can be com-
pensated by a full charge or by 1...3 char-
ging and discharging cycles.
red LED - 1 Vol%
red LED - 0.5 Vol%
95980004