UNDER NO CIRCUMSTANCES SHOULD ANY ATTEMPT BE MADE TO EITHER UNSCREW THE HEAT DETECTOR
ELEMENT FROM THE ENCLOSURE OR GAIN ACCESS TO THE INSIDE OF THE HEAT DETECTOR ELEMENT.
EITHER OF THESE ACTIONS WILL RESULT IN THE ASSEMBLY BECOMING UNSAFE FOR USE IN A POTENTIALLY
EXPLOSIVE ATMOSPHERE.
If you have acquired a significant quantity of Heat Detectors, then it is recommended that spares are also
made available, (please discuss your requirements with MEDC's Technical Sales Engineers).
5.0 CERTIFICATION
Model Dependant
Certified to EN50014:1997, EN50018:2000 EExd IIB T6.
ATEX Certificate No. Baseefa03ATEX0447
Certified to
EN50014:1997,
EN50019: 2000,
EN50028: 1997 EExem II T6
ATEX Certificate No.
Baseefa 03ATEX0428
The ATEX certificate and the product label carry the ATEX group and category marking:
II 2G
Where:
signifies compliance with ATEX
II signifies suitability for use in surface industries
2 signifies suitability for use in a zone 1 area
G signifies suitability for use in the presence of gases
Certified to
EN50014:1997,
EN50020:2002,
EN50284:1999 EExia IIC T6
ATEX Certificate No.
Baseefa 03ATEX0427
The ATEX certificate and the product label carry the ATEX group and category marking:
II 1G
Where:
signifies compliance with ATEX
II
signifies suitability for use in surface industries
1
signifies suitability for use in a zone 0 area
G signifies suitability for use in the presence of gases
© MEDC 2003