6. Connection and start-up

Voltage supply and programming
The voltage supply for the evaluation
units is connected to plug C1 (see the fig-
ure on page 18), V+ and
Insulation from the mains must be
ensured in accordance with the respective
standards. A safe separation is not
required.
If a power supply with safe separation is
used, this power supply may simultane-
ously supply other equipment which
requires no supply with safe separation.
Equipment which requires a supply with safe separation must not be
supplied simultaneously with the evaluation unit.
Depending on the number of the con-
nected safety switches programming is
required.
If the number of the connected safety
switches is odd, the jumper between
pins P1/P2 must be present.
18 ... 30 V
.
+
-
18 ... 30 V
+
-
V+
P2
P1
other
equipment
V+
P2
jumper P1/P2
closed
P1
L-
A TE L+
L +
TE
A
L
L +
TE
A
L
L +
TE
A
L