DATI TECNICI - TECHNICAL DATA - DONNÉES TECHNIQUES - DATOS TÉCNICOS - TECHNISCHE DATEN - DATOS TÉCNICOS - TECHNISCHE DATEN
Secondo Norma EN 50470-1, EN 50470-3, EN 62053-23, EN 62053-31 - Data in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31 - Selon les normes EN 50470-1, EN 50470-3,
EN 62053-23, EN 62053-31 - Secondo Norma EN 50470-1, EN 50470-3, EN 62053-23, EN 62053-31 - Daten nach EN 50470-1, EN 50470-3, EN 62053-23 und EN 62053-23
ITALIANO
Caratteristiche generali
Custodia DIN 43880: 4 Mod.
Fissaggio EN 60715: binario DIN 35 mm
Profondità:
70 mm
Funzionamento
Connessione a rete monofase / trifase N° fili: 2-4
Memor. energia mis. e configurazione: memoria interna Flash
Tariffa per energia attiva e reattiva:
n°2 T1-T2
Parametri di approvazione (secondo EN 50470-1 e EN 50470-3)
Tensione di riferimento (Un), Linea-Neutro: 230 VAC
Tensione di riferimento (Un), Linea-Linea: 400 VAC
Corrente di riferimento (Iref): 5 A
Corrente minima (Imin): 0,25 A
Corrente massima (Imax): 80 A
Corrente iniziale (Ist): 0,015 A
Frequenza di riferimento (fn): 50 Hz
Numero di fasi (numero di fili): 1,3 (2,4)
Classe di precisione (secondo EN 50470-3): B
Tensione di alimentazione e potenza consumata
Intervallo operativo di alimentazione: 110 ... 276 / 190 ... 480 VAC
Potenza assorbita (Circuito di tensione): ≤ 2 VA (0,6 W)
Potenza assorbita a corrente Imax (Circuito di corrente): ≤ 0,7 VA
Sovraccarico
Tensione Un
permanente; fase/fase: 480 VAC
1 secondo: fase/fase: 800 VAC
permanente; fase/N: 276 VAC
1 secondo: fase/N: 300 VAC
Corrente Imax
permanente: 80 A
momentanea (10 ms): 2400 A
Caratteristiche dei circuiti di misura
Campo di misura della tensione: fase/fase 190 ... 480 VAC
fase/N 110 ... 276 VAC
Campo di misura della corrente: 0,015 ... 80 A
Campo operativo di frequenza: 48 ... 62 Hz
Valori Misurati: MWh, Mvarh, kWh, kvarh, MW, Mvar, kW, kvar
Visualizzazione dati
Energia attiva (6 cifre + 2 cifre decimali): 0,01 ... 999999,99 kWh
Energia Reattiva (6 cifre + 2 cifre decimali): 0,01 ... 999999,99 kvarh
Potenza attiva istantanea (← e →) 3 cifre: 0 ... 999 MW, kW, W
Potenza reattiva istantanea (← e →) 3 cifre: 0 ... 999 Mvar, kvar, var
Bargraph della potenza, 10 segmenti: 0% -10% -20% ... -100%
Tariffa vigente: T1 - T2
Uscite a impulsi (uscite S0, secondo la IEC 62053-31)
Uscita a Impulsi 1, proporzionale ad energia attiva importata: kWh (→)
Uscita a Impulsi 2, proporzionale ad energia reattiva importata: kvarh(→)
Frequenza di impulsi: 500 p/kWh - p/kvarh
Durata impulso ON: 50 ± 2% msec
Tensione operativa impulsi, Min.-Max. : 5 ... 33 VAC (5 ... 70 VDC)
Massima corrente di impulso ON: 90 mA
Interfaccia ottica (LED metrologico)
LED rosso visibile sul frontale, proporzionale ad energia attiva (← e →):
1000 p/kWh
Sicurezza
Classe di isolamento: II
Tensione di prova (EN 50470-3, 7,2): 4 kV
Classe inquinamento: 2
Prova tensione di impulso: 6 1,2/50 ms-kV
Resistenza della custodia alla fiamma, UL 94: classe V0
Morsetti di connessione
Tipo di gabbia morsetto principale, testa della vite Z +/-: PZ2 POZIDRIV
Tipo di gabbia morsetto uscita impulso, testa della vite a taglio: 0,8x3,5 mm
Capacità morsetto principale:
filo compatto min. (max): 1,5 (35) mm
filo flessibile con capocorda min. (max): 1,5 (35) mm
Capacità morsetto uscita impulso:
filo compatto min. (max): 1 (4) mm
2
filo flessibile con capocorda min. (max): 1 (2,5) mm
Condizioni ambientali (immagazzinamento)
Campo di temperatura: -25 ... +70 °C
1
2
~
Tarife
Tariff
Condizioni ambientali (operative)
Campo di temperatura: -25 ... +55 °C
Condizioni ambientali meccaniche: M1
Condizioni ambientali elettromagnetiche: E2
Installazione, ambienti Interni: si
Altitudine (max.): ≤ 2000 m
Umidità, media annuale (non condensante): ≤ 75 %
per 30 giorni l'anno (non condensante): ≤ 95 %
Grado IP: IP51(*)/IP20
(*) Grado di protezione garantito in un quadro con almeno grado di
protezione IP51
General characteristics
Housing DIN 43880:
Mounting EN 60715:
Depth:
Operating features
Connection to single/three phase network N° wires: 2-4
Storage of energy values and configuration: Internal flash memory
Tariff for active and reactive energy, n°2: T1, T2
Approval (according to EN 50470-1, EN 50470-3)
Reference voltage (Un), Line to Neutral: 230 VAC
Reference voltage (Un), Line to Line: 400 VAC
Reference current (Iref): 5 A
Minimum current (Imin): 0,25 A
Maximum current (Imax): 80 A
Starting current (Ist): 0,015 A
Reference frequency (fn): 50 Hz
Number of phases (number of wires): 1,3 (2,4)
Accuracy class (according to EN 50470-3): B class
Supply Voltage and Power Consumption
Operating supply voltage range: 110 ... 276 / 190 ... 480 VAC
Power absorbed (Voltage circuit): ≤ 2 VA (0,6 W)
Power absorbed (Current circuit), Imax: ≤ 0,7 VA
Overload capability
Voltage
Current
Measuring features
Voltage range: phase/phase: 190 ... 480 VAC
phase/N: 110 ... 276 VAC
Current range: 0,015 ... 80 A
Frequency range: 48 ... 62 Hz
Measured quantities: MWh, Mvarh, kWh, kvarh, MW, Mvar, kW, kvar
Display features
Active energy, 6 digits + 2 decimal digits: 0.01 ... 999999.99 kWh
Reactive energy, 6 digits + 2 decimal digits: 0.01 ... 999999.99 kvarh
Instantaneous active power (← e →), 3 digits: 0 ... 999 MW, kW, W
Instantaneous active power (← e →), 3 digits + capacitive/inductive
indication: 0 ... 999 Mvar - kvar - var
Power bargraph, 10 segments: 0% -10% -20% ... -100%
Running tariff: T1 or T2
Pulse outputs (S0 signals, acc. to IEC 62053-31)
Pulse ouput 1, proportional to active imported energy: kWh (→)
Pulse ouput 2, proportional to reactive imported energy: kvarh (→)
Pulse rate: 500 p/kWh - p/kvarh
Pulse ON duration: 50 ± 2% msec
Operating voltage, Min. - Max.: 5 ... 33 VAC (5 ... 70 VDC)
Pulse ON maximum current: 90 mA
2
Optical Interface (metrological LED)
Front mounted red LED, proportional to active imp/exp Energy: 1000
2
p/kWh
Safety
2
Protective class: class II
AC voltage test (EN 50470-3, 7,2): 4 kV
Degree of pollution: 2
Impulse voltage test: 6 1,2/50 ms-kV
Conteggio energia su contatore T2 - Energy count on meter T2 - Comptage d'énergie sur le
compteur T2 - Conteo energía en el contador T2 - Stromzählung auf Zähler T2
ENGLISH
4 Mod.
DIN rail 35 mm
70 mm
continuous; phase/phase: 480 VAC
1 second, phase/phase: 800 VAC
continuous; phase/N: 276 VAC
1 second, phase/N: 300 VAC
continuous: 80 A
momentary (10 ms): 2400 A
230 V~
1
2
~
Tarife
Tariff
Housing material flame resistance, UL 94: class V0
Connection terminals
Type cage main paths, screw head Z +/-: PZ2 POZIDRIV
Type cage pulse output, blade for slotted screw: 0.8 x 3.5 mm
Terminal capacity main paths:
solid wire min. (max): 1,5 (35) mm
2
stranded wire with sleeve min. (max): 1,5 (35) mm
Terminal capacity pulse output:
solid wire min. (max): 1 (4) mm
2
stranded wire with sleeve min. (max): 1 (2.5) mm
Environmental conditions (storage)
Temperature range: -25 ... +70 °C
Environmental conditions (operating)
Temperature range: -25 ... +55 °C
Mechanical environment: M1
Electromegnetic environment: E2
Installation, indoor: yes
Altitude (max.): ≤ 2000 m
Humidity, yearly average, not condensing: ≤ 75%
on 30 days per year (not condensing): ≤ 95%
IP rating: IP51(*)/IP20
(*) For the installation in a cabinet at least with IP51 protection.
FRANÇAIS
Caractéristiques générales
Boîtier DIN 43880:
4 Mod.
Fixation EN 60715:
binaire DIN 35 mm
Profondeur:
70 mm
Fonctionnement
Branchement sur réseau monophasé / triphasé Nombre de fils: 2-4
Mémoris. de l'énergie mesurée et configuration: mémoire Flash interne
Tarif pour énergie active et réactive: n°2 T1-T2
Paramètres d'approbation (conformément aux normes EN 50470-1 et EN
50470-3)
Tension de référence (Un), Ligne-Neutre: 230 VAC
Tension de référence (Un), Ligne-Ligne: 400 VAC
Courant de référence (Iref):
5 A
Courant minimal (Imin):
0,25 A
Courant maximal (Imax):
80 A
Courant initial (Ist):
0,015 A
Fréquence de référence (fn):
50 Hz
Nombre de phases (nombre de fils):
1,3 (2,4)
Indice de classe (conformément à la norme EN 50470-3): B
Tension d'alimentation et puissance consommée
Intervalle fonctionnel d'alimentation : 110 ... 276 / 190 ... 480 VAC
Puissance absorbée (Circuit de tension) : ≤ 2 VA (0,6 W)
Puissance absorbée à courant Imax (Circuit de courant) : ≤ 0,7 VA
Surcharge
Tension Un
permanente, phase/phase: 480 VAC
1 seconde, phase/phase: 800 VAC
permanente, phase/N: 276 VAC
1 seconde, phase/N: 300 VAC
Intensité Imax:
permanente: 80A
momentanée (10 ms): 2400 A
Caractéristiques des circuits de mesure
Gamme de mesure de la tension, phase/phase: 190 ... 480 VAC
phase/N: 110 ... 276 VAC
Gamme de mesure du courant: 0,015 ... 80 A
Gamme fonctionnelle de fréquence: 48 ... 62 Hz
Valeurs mesurées: MWh, Mvarh, kWh, kvarh, MW, Mvar, kW, kvar
Affichage données
Énergie active (6 chiffres + 2 chiffres décimaux): 0,01 ... 999999,99 kWh
Énergie réactive (6 chiffres + 2 chiffres décimaux): 0,01 ... 999999,99 kvarh
Puissance active instantanée (← et →) 3 chiffres: 0 ... 999 MW, kW, W
Puissance réactive instantanée (← et →) 3 chiffres: 0 ... 999 Mvar, kvar, var
Graphique à barres de la puissance, 10 segments: 0% -10% -20% ... -100%
Tarif en vigueur: T1 - T2
Sorties à impulsions (sortie S0, conformément à la norme CEI 62053-31)
Sorties à impulsions 1, proportionnel à l'énergie active importée: kWh (→)
2
2