WARNING: the installation of the device must be exclusively done by
qualified personnel, following the regulations in force and the
guidelines for KNX/EIB installations.

Warnings for KNX/EIB installations

1. The length of the bus line between the 4 channel 16 A Easy actuator and the power
supply unit must not exceed 350 metres.
2. The length of the bus line between the 4 channel 16 A Easy actuator and the most
distant KNX/EIB device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable signals and
overloads.
4. Keep a distance of at least 4 mm between the individually insulated cables of the bus
line and those of the electric line (figure C).
5. Do not damage the electrical continuity conductor of the shielding (figure D).
WARNING: the unused bus signal cables and the electrical continuity
conductor must never touch elements under power or the earth
conductor!
Fit the 4 channel actuator to a 35 mm DIN rail as follows (figure E):
1. Insert the device's upper coupling in the DIN rail.
2. Rotate the device until a "click" is heard, signalling locking to the DIN rail.