The 4 channel 16 A Easy Actuator – DIN rail allows you to individually
activate/deactivate up to 4 different electrical loads using 4 16 A relays fitted with 1
NO output contact each. The relay switching command can be given by Home
Automation control or sensor devices using the KNX/EIB bus, or it can be generated
locally using the front buttons.
The actuator is powered by the bus line and is fitted with 4 front green LEDs which
indicate the output status.
This device sends to the bus information on the relay status (ON= NO contact closed,
OFF= NO contact open) at the ignition, at the reception of a command and when it is
commanded via the local button.
Each actuator output channel can be configured individually and foresees the ON/OFF
command for the loads, the execution of timed commands, scene management and the
implementation of priority commands to override the output status. The operating
methods can be used simultaneously.
This means, for instance, that the device can turn a light on or off, or turn it on or off
automatically after a set time has elapsed according to the command received.
The module is fitted on a DIN rail, inside electric panels or junction boxes.
Each actuator channel can be configured with the Easy controller to perform one of the
following functions:
ACTIVATING AND DEACTIVATING LOADS
The actuator channel activates or deactivates the electric load when it receives ON/OFF
commands sent, for example, by a contact interface or a button pad configured in ON/OFF
Cyclic switching or Edge management mode.
The green LED comes on to indicate that the relay contact is closed.
TIMER COMMANDS
The actuator activates the connected electric load for the time determined by the
activation Time parameter and deactivates when it elapses. This is the setting for the
staircase light, for example. If the dimmer actuator receives another timer ON command
during the activation time, the time count restarts from the beginning.

GENERAL DESCRIPTION

To summarize
Functions