Herunterladen Inhalt Inhalt Diese Seite drucken

Operating Instructions - Grasslin talis II Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Operating manual
talis II PHB 360-20-1i – presence detector
Safety
Risk of fatal electric shock!
Only allow a qualified electrician to
install and connect the device.
WARNING!
• Before installing the product, disconnect the
mains voltage!
• Before installation, a type C circuit breaker
(250 VAC, 10 A) should be installed, in accord-
ance with EN60898-1.
• When lamps from some manufacturers burn
out, they can cause a high inrush current,
which can permanently damage the detector.
• Observe the national regulations and safety
conditions.
• Interventions in and modifications to the device
shall result in loss of warranty and guarantee.
Read and observe this manual in order to ensure
trouble-free functioning of the device and safe
work.
For more information:
http://qrc.graesslin.de/801015287
Information about the device
Description of the device
The presence detector operates on the principle of
passive infra-red sensors (PIR sensor). It automat-
ically regulates the connected loads according to
whether persons are present (movement detection)
and according to the ambient brightness. The built-in
light sensor continuously measures the strength of
daylight and the system compares this against the
set lux value.
• The light remains switched on for as long
as movement and insufficient daylight are
detected.
• After the last movement is detected, the lighting
remains switched on for the set run-on time.
• The lighting switches off automatically as soon
as sufficient ambient brightness is reached,
even if movement is detected during this time.
• The presence detector is suitable for use in
indoor spaces.
Technical data
Supply voltage
Detection range
Range
Time setting
METER
LUX
Light value
2000
300
Ambient temperature
100
Protection class
IP code
Energy consumption
230 V~ ±10% 50/60 Hz
360°
approx. Ø 20 m (Fig. 6)
approx. 30 sec. – 30 min.;
TIME
; test
1s
Test
approx. 10 lux – " ";
30m
5s
10
"
" = learning mode
5m
-20 °C to +45 °C
15m
II
IP20
IP54 for on-wall mounting
< 1 W (in standby mode)
EN
7

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis