Herunterladen Inhalt Inhalt Diese Seite drucken

CAME BPT TH/450 GSM Bedienungsanleitung Seite 60

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

J
TH450
The graph and table K can help you decide on the type of program or value of the pa-
rameter to be added.
Press button P to exit programming.
N.B. All parameters related to the configuration of the type of temperature management
algorithm are saved in the permanent memory of the device.
K
Cycle length
Prog.
(minutes)
P1
10
P2
5
P3
20
P4
from 5 to 40 from 1 to 5
OFF
ON
1 h
Minimum ON
Proportional
time (minutes)
band
1
1.5 °C
1
1.5 °C
2
1.5 °C
from 1 °C to
3 °C
Press button P J to confirm the
minimum ON time and switch to
adjusting the proportional band.
Use the
value of the proportional band to
between 1 and 3 °C.
ON
Setpoint
Time
Type of system
Base for gas burner, fan coils, zone valves,
aluminium radiators
Electric radiators
Radiant or underfloor systems, cooling
buttons to adjust the

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis