TECHNICAL DATA
i-CHD U-2T
Models
Version
Air flow rate
Vel.3
Vel.2
Vel.1
Total cooling capacity (1)
Vel.3
Vel.2
Vel.1
Sensible cooling capacity (1)
Vel.3
Vel.2
Vel.1
Max water flow
Max pressure drop
Total heating capacity (2)
Vel.3
Vel.2
Vel.1
Max water flow
Max pressure drop
Sound power level (4)
Vel.3
Vel.2
Vel.1
Technical characteritics
Water content
Water inlet fittings
Water outlet fittings
Max adsorbed power
Max adsorded current
Electrical power supply
Cassette dimensions with air grille
High
Width
Depth
Packaging (H×WxD)
Net Weight
Gross Weight
Data reffered to
(1)
Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
(2)
Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
(3)
Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
(4)
Sound power on the basis of measurements made in compliance with Eurovent 8/2
12
EN
i-CHD 706
U-2T
m
3
/h
200
m
3
/h
520
m
3
/h
810
kW
1,41
kW
3,28
kW
4,56
kW
1,11
kW
2,31
kW
3,17
m
3
/h
0,78
kPa
36,8
kW
2
kW
3,9
kW
6,15
m
3
/h
0,95
kPa
33
dB(A)
35
dB(A)
45
dB(A)
60
l
1,56
inch
3/4
inch
3/4
W
40
A
0,347
V-Ph-Hz
220-240/1/50
(mm)
575
(mm)
575
(mm)
290
(mm)
750x750x375
kg
30
kg
33
i-CHD 1108
i-CHD 2209
U-2T
U-2T
360
820
1380
1300
2100
3,13
5,87
5,1
6,9
10,6
2,52
4,84
3,85
5,06
8,11
1,18
1,82
31
3,91
6
10,3
8,3
12,6
1,44
2,28
26
39
53
67
1,78
2,41
3/4
3/4
88
0,765
1,739
220-240/1/50
220-240/1/50
730
730
290
910x910x375
1040x1040x375
36
40
General
820
8,6
7,1
36
7
34
42
58
66
3/4
3/4
200
830
830
290
50
55