28
en
NOTICE!
Installation must only be performed by authorized and specialized personnel!
For the scope of delivery, see Figure 1 on Page 4.
On the CD included, you will find the FSP-5000-RPS Programming Software and the required
documentation on the FPA-5000 and FPA-1200 including the operation guide and the wiring
guide.
WARNING!
Live components and stripped cable! Risk of injury from electric shock. The system must be
current-free during connection work.

Functional Description

The Panel Controller controls every component connected to the panel and features the following functional
elements (see Figure 1 III, Page 4):
Pos. Designation
A
Touch screen
B
22 fixed buttons
C
11 LEDs
D
Key switch
E
3 rotary switches
F
Reboot button
G
6-pin DIP switch
H
Ground wire
Installation
The FPA-1200-MPC Panel Controller is only used with the FPA-1200 Fire Panel.
The MPC-XXXX-B Panel Controller may be mounted into the following FPA-5000 housings:
CPH 0006 A, MPH 0010 A, HCP 0006 A and HBC 0010 A.
For the installation, follow the instructions given in Figure 2 to Figure 4 (Page 5 to Page 7):
Make sure that the PRS 0002 A Panel Rail Short is mounted before you start installing the Panel Controller.
Connect the ground wire to the screw on the housing (Step 4, Figure 3, Page 6).
Plug the cable into the slot labeled "IN" of the PRS 0002 A Panel Rail Short (Step 6, Figure 3, Page 6).
Note: Plugging the cable into the slot labeled "OUT" or into either slots of the PRD 0004 A Panel Rail Long is not
allowed.
Plug the EOL resistor for the databus into the slot labeled "OUT" of the last panel rail PRS/PRD in use (Step 8,
Figure 4, Page 7).
Wiring
The Panel Controller features
-
two CAN interfaces (CAN1/CAN2) for networking (bus or loop topology)
-
two signal inputs (IN1/IN2)
-
Ethernet , USB and RS232 interfaces
Consider the maximum cable length of 3 m when using the USB and RS232 interfaces (see Figure 5, Page 8).
The connection to a Building Management System (BIS) is done via an OPC server and the Ethernet 100BaseTX
interface. For a multiple-building network, you must check with the network adminstrator if
the network is designed for multiple-building connections (e.g. no technical interference by varying ground
potentials);
the bus users are designed for the network.
Address Setting and Configuration
Assign a unique physical address to each Panel Controller and Remote Keypad by setting the rotary switches and
write it down on the label (Step 1 and 2, Figure 7, Page 9). Make sure that the redundant panels do have identical
addresses. For configuration, set the 6-pin DIP switch (Step 3, Figure 7, Page 9). Mark the setting on the provided
label (Step 4).
On pages 10 to 19, you will find the different types of network topologies with the required DIP switch and address
settings.
F.01U.029.053 | 5.0 | 2009.10
Function
Operating the panel through virtual buttons and variable display windows
Standard entries
Indicating the operating status
2 switch settings, freely programmable, e.g. for switching between day/
night mode, or connection/disconnection to and from the local alarm
signaling
Address setting
Panel HW reset
Configuration
Grounding the panel
MPC-xxxx-B / FPA-1200-MPC
Bosch Sicherheitssyteme GmbH