Herunterladen Inhalt Inhalt Diese Seite drucken

Emerson FB2100 Anleitung Seite 7

Inhaltsverzeichnis

Werbung

Wiring to Communications & I/O
Connect the wiring to the terminal blocks on the I/O and
communications modules. Refer to either Section 2.8 in
Chapter 2 of the Emerson FB2100 Flow Computer
Instruction Manual (part D301783X012) or the Emerson
FB2100 Flow Computer Quick Start Guide (part
D301787X012) for wiring schematics and
explanations.
Once you have wired the communications and I/O,
close and secure the cover of FB2100.
Powering Up the FB2100
DANGER
Do not attempt to connect power or disconnect power
from the unit in a hazardous area. Ensure the area is
non-hazardous. Failure to do so could result in an
explosion.
1. To start up the FB2100, apply power.
When you turn power on, the backlight on the HMI
module lights for about 5 seconds, then turns off.
During this time the database begins to initialize.
After about 45 seconds the backlight on the HMI
turns on again and starts to display live data.
Periodically inspect the wiring for signs of
deterioration.
Configuring the FB2100
You must install Emerson's Field Tools configuration
software (which includes FBxConnect™) on your PC to
configure the FB2100 for use. Refer to the Emerson
FB2100 Flow Computer Quick Start Guide (part
D301787X012) for instructions on installing and using
this software.
Resetting the FB2100
If you are experiencing problems that appear to be
software related, try resetting the FB2100. Refer to the
Service and Troubleshooting chapter in the Emerson
FB2100 Flow Computer Instruction Manual (part
D301783X012) for specific instructions.
Note: You lose all configuration and log data with a
reset. If possible, make a backup of
configuration and log data before attempting
any type of reset.
Replacing Parts in the FB2100
Refer to
Table 1
for a list of user-serviceable parts and their
respective Field Replacement Guides.
www.Emerson.com/RemoteAutomation
Safe Use Instructions – Emerson FB2100 Flow Computer
Returning the FB2100
If you are experiencing problems that appear to be
hardware-related, verify the wiring. If you still experience
problems, contact your local sales office for return
authorization. To return the device:
1. Back up all configuration and data before removing
the device from process. Then remove power from
the device and remove all external wiring.
2. Uninstall the device.
3. Place the device into a box safe for shipping or
storage.
Part D301770X012
September 2018
5

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis