BMV can incorrectly indicate that the battery needs recharging.
When in this case Ith is set to 0.1, the BMV calculates with 0.0 A so
that errors are eliminated. A value of 0.0 disables this function.
Tdt:
Average time-to-go. Specifies the time window (in minutes) that the
moving averaging filter works with. Selecting the right time depends
on your installation. A value of 0 disables the filter and gives you
instantaneous (real-time) readout; however the displayed values may
fluctuate heavily. Selecting the highest time (12 minutes) ensures
that long term load fluctuations are included in the time-to-go
calculations.
DF:
Discharge floor. When the state-of-charge percentage has fallen
below this value, the alarm relay will be activated. The time-to-go
calculation is also linked to this value. It is recommended to keep this
value at around 50.0 %.
ClS:
Clear SOC relay. When the state-of-charge percentage has risen
above this value, the alarm relay will be de-activated. This value
needs to be greater than DF. When the value is equal to DF the relay
will not be activated depending on the state-of-charge percentage.
RME:
Relay minimum enable time. Specifies the minimum amount of time
the relay should be enabled.
RDD:
Relay disable delay. Specifies the amount of time the relay disable
condition must be present before acting upon it.
Al:
Alarm low voltage. When the battery voltage falls below this value for
more than 10 seconds the low voltage alarm is turned on.
Alc:
Clear low voltage alarm. When the battery voltage rises above this
value, the alarm is turned off. This value needs to be greater than or
equal to Al.
Ah:
Alarm high voltage. When the battery voltage rises above this value
for more than 10 seconds the high voltage alarm is turned on.
Ahc:
Clear high voltage alarm. When the battery voltage falls below this
value, the alarm is turned off. This value needs to be less than or
equal to Ah.
AS:
Alarm low SOC. When the state-of-charge falls below this value for
more than 10 seconds the low SOC alarm is turned on.
ASc:
Clear low SOC alarm. When the state-of-charge rises above this
value, the alarm is turned off. This value needs to be greater than or
equal to AS.
A BUZ: Determines whether or not the buzzer will sound during an alarm
condition. If enabled (indicated by an 'X'), the buzzer will sound when
an alarm condition is present. The alarm can be silenced by pressing
12