The models in this range offer the possibility
of working as hot/cold air curtains.
We advise you to check that the unit is in
perfect condition when unpacking it, as any
manufacturing or quality defect is covered by
the S&P guarantee.
IMPORTANT: SAFETY GUIDELINES
The appliance must not be right above or
below a socket.
Do not cover the unit with clothes or objects
that may obstruct the airflow and cause
overheating.
While in operation, the connection cable
must not be in front of the air outlet.
If it is installed in the bathroom, it must be
placed so that the switches or other control
devices cannot be touched by anyone in the
bathtub or shower.
There must not be any inflammable objects
at less than 50 cm from the unit (such as
window curtains, etc.).
Keep the inlet and outlet grilles clean. When
cleaning them, disconnect the unit from the
mains supply.
Do not manipulate the unit with wet hands.
The installation work must be carried out by
an electrician.
IMPORTANT: THIS APPLIANCE MUST BE
EARTHED.
The means of disconnection from the mains
supply must have an opening distance of at
least 3 mm in all poles.
To operate the unit as an Air Curtain, the
maximum distance to the floor must not be
greater than 10 metres.
The minimum distance between the Air
Curtain and the floor must be 4 metres.

INSTALLATION

The unit must be fixed to a convenient
surface.
The minimum distances shown in Fig. 1
must be kept.
To install the unit, proceed as follows:
If the spiral nuts already placed in the device
are used, the centres of the screws (M-12)
must be marked according to the table in Fig.
2 (a) and Fig. 2(b).
To access the connection cards you must
open the front grille by unscrewing the
screws marked "A" in Fig. 3. To close, follow
the process in reverse order.
The maximum working pressure of the water
radiator must not exceed 4 Kg/cm .
The maximum temperature of the hot water
must not exceed 95ºC.
The water coil must not operate at
temperatures of less than 5ºC. When there is
a risk of the temperature dropping below this
limit antifreeze liquid must be used or the
installation must be emptied.
The water pump must be connected to the
coil via the 3/4" gas thread inlets fitted for this
purpose.
ELECTRICAL CONNECTION Fig. 4
They are installed appliances. When
connecting them to the mains, the standards
and regulations in force in your country must
be strictly adhered to.
Within the installation an electrical isolation
switch must be present, to enable the
installer to cut all supply lines.
Connect the unit to the mains supply,
checking that the voltage and frequency are
the same as those indicated on the electrical
rating plate.
Use the cables with the number of wires and
sections as indicated on the wiring diagram
for every model.
Fix the cables with the clamp provided.
7
2