Herunterladen Diese Seite drucken

Protocol Data Package Composition - elobau 485EPF series Originalbetriebsanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PROTOCOL DATA PACKAGE COMPOSITION

The bus module exports the system status and the status and diagnostics elements of all I/Os configured
on the eloProg and enables 8 single field bus inputs to be imported.
The input and output memory maps are described in the tables at page 3.
The input map is made up by a single byte representing the fieldbus inputs.
The output map is made up by a status byte, a variable number of bytes for the Mosaic input status, a
byte representing the copy of the fieldbus inputs, a variable number of bytes to represent the probes
status, a variable number of bytes to represent the Mosaic OSSD status, two bytes to represent the
Mosaic diagnostics.
The system status is shown as 1 byte in which the 0 bit indicates whether the eloProg is online/offline
and bit 1 indicates the presence of diagnostics elements.
Each input and each output (OSSD) configured on the system is associated with two information
elements: status and diagnostics.
Status is a binary value, 0 or 1, diagnostics is a code indicating the condition of the I/O, which can be OK
or indicate a problem on the I/O.
Each module with inputs has a number of bits corresponding to the number of physical inputs which are
present; thus the modules 485 EPB, 485 EPE08, 485EPE08A02 are associated with 1 byte (8 bit), the
modules 485EPE16, 485EPE12 with 2 bytes (16 bit) for the inputs status.
All safety outputs are summarized in 1 or 2 bytes.
The location of the inputs varies according to the type of modules that are installed, in the following
order: 485EPB, 485EPE08A02, 485EPE16, 485EPE08, 485EPE12. If several modules of the same type
are installed the order follows the node number.
Diagnostics elements are in the form of 2 bytes which indicate the number of the I/O with the problem
and the value of the diagnostics element. If there is more than one diagnostics element, the relative
values alternate every 500 ms. Each set of information:
input status,
-
input diagnostics,
-
field bus input status,
-
probe status,
-
safety output status,
-
safety output diagnostics
-
can be enabled/disabled in order to control the information and thus the number of bytes exported to the
field bus. The field bus inputs are 8 independent bits through which 8 different states can be injected into
the electrical panel.
The byte that represents the 8 field bus inputs is mapped as the first PLC input byte.
For the fieldbuses in which the mapping position is mandatory (i.e. PROFIBUS DP) the input byte
must be mapped before the output bytes.
For the fieldbuses based on CANOpen the data can be accessed only via PDO. The SDO access is
not supported.
eloProg 485EPF.. - Vers. 1.2
4

Werbung

Kapitel

loading