16
en
Description
IN
IN+ | IN-
OUT
POW+
OUT-
POWER IN
POW+ | POW-
LSN
b1+ | a- | b2+

Technical Specification

LSN input voltage
Max. current consumption from LSN
Output
Max. switched voltage of outputs
Max. output current rating
External power supply
Input monitoring functions:
1. Line monitoring with EOL:
EOL resistor
Overall line resistance R
(R
= R
+ R
+ R
Σ
L/2
L/2
2. Contact monitoring:
Max. current strength (current pulse)
Minimum activation time of the input
Max. cable length input
Max. cable length output
Maximum cable length of all inputs and outputs
which are connected to the loop or stub and
not electrically isolated from LSN
Permissible wire diameter
Permissible operating temperature
Permissible storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Material and color
Dimensions (with adapter)
F.01U.032.854 | 1.0 | 2008.10
Function
Input
Reference potential (+)
Output (switched negative potential)
Power supply output (OUT)
LSN (incoming/outgoing)
Σ
)
EOL
15 - 33 V DC (min. - max.)
1,9 mA
30 V DC
700 mA (depending on external power supply)
5 to 30 V DC (min. to max.)
Nominal 3,9 kΩ
In standby: 1500 Ω to 6000 Ω
Short-circuit: < 800 Ω
Interruption: > 12000 Ω
8 mA
3.2 s
3 m
3 m
500 m in total
2
0,6 to 3,3 mm
-20 °C to +65 °C
-25 °C to +80 °C
<96%, non-condensing
IP 30
Class III equipment
PPO (Noryl), gray white (similar to RAL 9002)
Approx. 110 x 110 x 48 mm (W x H x D)
FLM-420-O1I1-D
Bosch Sicherheitssysteme GmbH