The DIL control unit can be used to control 1 motor with power not exceeding 1500W.
a) The wire connections and the operating logic should be in compliance with regulations in force.
b) The cables featuring different voltage should be physically separated, or adequately insulated by
an additional insulation of at least 1 mm.
c) The cables should be further fastened in proximity to the terminals.
d) Check all connections before powering the unit.
e) Check that setting of the Dip-Switches are the required ones.
f) Normally Closed inputs which are not in use should be short-circuited.
Terminals
Function
1-2-3-4
Motor
5-6-7
Power supply Input 230Vac 50/60Hz (5-GND/6-Phase/7-Neutral).
8-9
24Vdc
Safety
8-10
devices
8-11
Step-by-Step
8-12
Close
F1
Fuse, motor protection
1)
Turn power off.
2)
Manually release the door and push it for about half stoke. Lock the door again.
3)
Turn power on.
4)
Send a step-by-step or radio-control signal.
5)
The door must move in the opening phase. In the negative, with motor stopped, invert the wires
(3/5) of the motor.
The stoke learning (working time) is carried out as follows:
- Bring the leaf to the fully close position
- Hold down the button S1, the motor starts opening.
- Wait for the complete opening (wait a few seconds more to gain some margin) and then release the
button S1, the new working time is now stored.
8
DIL Control Unit
GENERAL WARNINGS
INPUT/OUTPUT FUNCTIONS
Description
Connection to motor
(1-start/2-Com/3-start/4-GND).
Accessories power supply output, 24VAC/100 mA max
Terminal 8 (0Vdc) can be also used as common terminal for the
control inputs.
Input for safety devices (photocell /safety edge), configurable as
N.C. / N.O. / 8k2 through Dip-Switch1.
SAFE LED is on if the connected safety device is OK (consent to
move), it is off if the safety device is K.O. (no consent)
Input, Step-by-step or OPEN push-button (N.O. contact), configurable
through Dip-Switch 2. LED PP lights up when the contact is activated.
Input, CLOSE push-button (N.O. contact). LED CLOSE lights up
when the contact is activated.
FUSES
HOW TO CHECK CONNECTIONS:
STROKE SELF-LEARNING