Herunterladen Inhalt Inhalt Diese Seite drucken

SOMFY animeo Connect Gebrauchsanweisung Seite 8

Ip sensor gateway
Vorschau ausblenden Andere Handbücher für animeo Connect:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 7
EN
A
MOUNTING
[1] Wall mounted
[2] Din-rail mounted
B
WIRING
Complete the wiring and connect 24 V Power Supply.
Power supply needs to provide up to 24 V DC 900 mA to RS485 bus.
[1] Wiring diagram
[2] At the beginning and at the end of the 2-wired RS485 network a 120 Ohm resistance is essential.
m Terminator must not be removed unless a second weather station is connected.
m Do not connect more than 2 weather stations to the gateway. Take care of the consumption.
The cable used for the IP Ethernet connection must be a shielded cable. The shield needs to be connected on both ends.
Not compatible with PoE switch.
n
C
COMMISSIONING AND OPERATING
Complete installation of all devices.
Connect the PC to the IP input.
Run the animeo Connect Operating Software and follow the procedure described in the software guide.
A. „xx" represents the bus system handled by the gateway, e.g. io, SDN, ...
CHARACTERISTICS
Supply voltage
Power Supply
Minimum current
Max. current
Minimum power
Supply voltage of sensor bus/output
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Protection class
Degree of protection
Conformity
CABLE
Connection to ...
Power Supply
Ethernet
RS485 Bus
Power Supply (bus)
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
24 V DC +/- 10 % SELV/1 A max.
Mandatory use of certified power supply with limited power (certified according to the
relevant version of 60950-1 or 62368-1, EN/IEC or UL as needed in the country of use).
Limited power classified as LPS, PS2 or UL class II (according to standard)
32 mA
1 A@24 V
0.77 W
24 V DC +/- 10 %
0 ° C ... + 50 ° C
85 % at 30 ° C
ABS
133 x 86 x 44 mm
III
IP20
www.somfy.com/ce
Cable
Cat. 6
Min.: 2 x 0.3 mm
/22 AWG
2
Max.: 2 x 0.5 mm
/20 AWG
2
Min.: 2 x 0.3 mm
/22 AWG
2
Max.: 2 x 0.5 mm
/20 AWG
2
Twisted pair
Max. length
1.8 m
100 m
Required
300 m
Required
300 m
animeo Connect . IP Sensor Gateway . Ref. 5137983A -
8/20

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis