Thermokon Sensortechnik GmbH • www.thermokon.de • email@thermokon.de
Installation and operating instructions
Radio actuator SRC-DO lighting 230V for
radio sensors with Enocean technology
Art.no.: 335027
1. Description
Different consumers such as incandescent lamps, high-
voltage halogen lamps, electronic ballast and inductive loads
can be switched with the output 1 (channel 1) of the radio
actuator. The radio actuator is controlled by radio signals
from radio sensors. Each radio sensor can simultaneously
control an unlimited number of radio actuators.
The radio sensors have a fixed address and must be assigned
on a radio actuator (max. 32 radio sensors). The memory of
each radio actuator is empty when delivered.
Function 1 (two-button function) is preset by default in the
radio actuator of a freshly assigned radio sensor.
The radio actuator's function can be changed by programming
to respond to any assigned radio sensor (see Point 6).
2. Mounting
1
230V~
50Hz
L max.2500W
N N L L 1
N N L L 1
Learn
LED = red
Function programming:
LED = green oder orange
N
L
Mounting and set-up may only be carried out by an authorised
professional. All works may only be performed once the
mains power supply 230V/50Hz~ has been switched off.
Mounting must adhere to the valid laws, standards and
regulations. The supply line may only be fused with a fuse
or circuit breaker (max. 16A).
For programming, the radio actuator must be connected to
the mains power supply. The programming is retained even
in a power failure.
NEVER mount the radio sensor or radio actuator in a metal
housing or directly next to large metal objects.
It is also not advisable to mount the radio actuators on the
floor or close to the floor.
The following points must be observed:
- the valid laws, standards and regulations
- the best available technology at the time of installation.
- the operating instructions of the Thermokon radio products.
- the fact that operating instructions can only contain general
guidelines and that these must be considered in the context
of a specific system.
Caution!! The Thermokon radio products must not be used
with devices, which could affect human health or safety, or
endanger humans, animals or material assets.
3. Technical data
Transmission frequency 868.3 MHz
Power supply
230 V~ / 50 Hz
Fusing the supply lines
Circuit breaker or fuse
(max. 16 A)
Incandescent lamp: 2500W
Consumer connection
data
HV-halogen lamps: 250W
Inductive load: 600 VA
Electronic ballast: 3 units
Ambient temperature
-20° to +40°C
Storage temperature
-40° to +85°C
Test specifications
EN 60669-2-1
Certifications
CE
IP 20
Protection level
TK-335027-Rev01_070223.pdf
GB
4. Assigning or deleting radio sensors
Radio sensors can be assigned or deleted in the learn mode
of the radio actuator.
Learn mode is activated by pressing the LRN/SET button
and the channel 1 is active (LED flashes red).
If a button of the radio sensor that is to be assigned is
pressed once in learn mode and recognized by the radio
actuator (LED on), the radio sensor has been assigned.
If a button of an already assigned radio sensor is pressed
once and recognized by the radio actuator (LED off), the
radio sensor has been deleted.
Caution!! If the button off a radio sensor is pressed repeatedly
the radio sensor will be alternately assigned or deleted!
After a radio sensor has been assigned or deleted the radio
actuator returns to learn mode (LED flashes red) and other
radio sensors can be assigned or deleted. When no button of
a radio sensor is pressed, the radio actuator leaves the learn
mode after approx. 30s independently.
Press the LRN/SET
button briefly
Learn mode channel 1
(LED flashes red)
CLR/MODE-button
Parameter setting
LRN/SET-button
Press the LRN/SET
with LED
button briefly
Learn mode and
Function
programming
Learn mode OFF
mode:
(LED off)
Function 1 (two-button function) is preset by default in the
radio actuator of a freshly assigned radio sensor.
If desired, the radio actuator's function and its parameter
can be changed by function programming (see Point 6) for
each assigned radio sensor.
5. Deleting all assigned radio sensors
Press the CLR/MODE button and hold it down for approx.
2s. During this time, the memory is completely deleted
(delivery status).
Then, the radio actuator is in learn mode (LED flashes red).
Press the CLR/MODE
button for longer
All assigned
radio sensors deleted
Learn mode channel 1
(LED flashes red)
6. Function programming
The radio actuator's function and its parameter can be
changed by function programming each assigned radio
sensor (see Point 4).
Function programming is activated by pressing an holding the
LRN/SET button until confirmed (LEDs flash green rapidly).
Function programming can be manually terminated by
activating the CLR/MODE button. Without activating the
button on a radio sensor, the radio actuator will terminate
function programming automatically after about 30s.
If function programming is active, a button of the radio
sensor must be pressed for recognition, for which the function
of the radio actuator is to be changed.
Once the radio sensor is recognized by the radio actuator, the
radio actuator's channel 1 is active (LED flashes orange).
The number of times the LED flashes corresponds to the
radio actuator's current function. This function can then be
changed by the number of times that the LRN/SET button is
activated (e.g. pressing LRN/SET twice = Function 2).
The parameter setting is accessed in function programming
by activating the CLR/MODE button. Channel 1 then becomes
active (LED flashes green).
Parameter setting can be manually terminated by activating
Assign/delete radio sensor
the CLR/MODE button.
Press a button of the
radio sensor once
The number of times the LED flashes corresponds to the
parameter currently set for the radio actuator's current
Radio sensor assigned
function. This parameter can then be changed by the number
(LED on)
of times that the LRN/SET button is activated
radio actuator function 1
(e.g. pressing LRN/SET twice = Parameter 2).
Radio sensor deleted
(LED off)
s. Point 4
Press the LRN/SET
button for longer
Function programming
(LEDs flash green rapidly)
Recognition of radio sensor
Press a button of the radio sensor
Channel 1 is active
(LED flashes orange)
number of flashing = function
Press the LRN/SET button to
select the function 1-8
number of actuations = function!
Press the CLR/MODE
button briefly
Parameter setting
Channel 1 is active
(LED flashes green)
number of flashing = parameter
Press the LRN/SET button to
select the parameter
number of actuations = parameter!
Idle state
(LED off)
Press the CLR/MODE
button briefly
GB - 1