Herunterladen Inhalt Inhalt Diese Seite drucken

TDK-Lambda DRB480-xx-1 Serie Handbuch Seite 19

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
DRB480-xx-1 Handbook
DRB-480 Handbook
10. DRB480-xx-1 series UL508 Listed Condition
1) Wire Requirement
Use minimum 75°C wire
Use copper conductor only
Ensure rated for current and voltage
Connections
Description
+V:
+ve output terminal
- V:
-ve output terminal
- DC
-ve input to DC OK terminal ( opto-coupler emitter)
+ve input to DC OK terminal (opto-coupler
+ OK
collector)
L:
Live AC input
N:
Neutral AC input
Protective Earth
* 4.4 lbf.in
2) For use in a Pollution degree 2 environment only
3) These products are considered for use where maximum surrounding air temperature does not exceed 70°C.
4) Indoor use only
11. DRB480-xx-1 outline drawings
Page 19 of 21
Recommended
Max. Torque*
10 – 16 AWG
0.5 Nm
10 – 16 AWG
0.5 Nm
10 – 24 AWG
0.5 Nm
10 – 24 AWG
0.5 Nm
10 – 18 AWG
0.5 Nm
10 – 18 AWG
0.5 Nm
10 – 18 AWG
0.5 Nm
260235 Rev 3, March 2019