MicroLogix™ Ethernet Interface (ENI)
Panel Mounting
Template
See back cover for panel mounting template.
Installation
ATTENTION
!
Mounting
Template
External Power Supply Wiring
WARNING
!
IMPORTANT
24
VDC
DC
NEUT
CHS
GND
Bottom View
Publication 1761-IN006B-MU-P
Be careful of metal chips when drilling mounting holes
for your equipment within the enclosure or panel. Drilled
fragments that fall into the equipment could cause
damage. Do not drill holes above mounted equipment if
the protective debris strip has been removed.
1. Remove the mounting template from the back of
this document.
2. Secure the template to the mounting surface.
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the unit.
EXPLOSION HAZARD - In Class I Division 2 applications,
an external, Class 2 power supply must be used. The DC
Power Source selector switch on the ENI must be set to
EXTERNAL before connecting the power supply to the
ENI.
• In non-hazardous locations, external power is not
required. Some devices (such as a MicroLogix
controller) provide power to the ENI via a cable
connected to ENI port 2. Be sure to set the DC power
source selector switch to match your particular
configuration, CABLE or EXTERNAL.
• Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This connection
must be made whether or not an external 24V dc
supply is used.
• wiring torque:
1.3 Nm (12 in-lb) rated; 1.4 (13 in-lb) maximum
wire size: #14 to #24 AWG