I I Setting of switch point (SP) / trigger point (TP)
The switch point is preset at the factory (LED 7).It is always higher than
the trigger point.
Setting range for SP: TP ↔ LED 9,
setting range for TP: LED 0 ↔ SP.
M
S
1
1 x (SP)
2 x (TP)
M
S
>5 s
2
M
S
3
*Decrease SP / TP: Let the flashing and lit LEDs move to the maximum setting
value. Then the cycle starts again at the minimum setting
value.
**Overflow: If the flashing LED and the lit LED exceed the maximum setting
value, the cycle starts again at the minimum setting value.
32
LO
LO
LO
LO
Press the Mode/Enter button
HI
once or twice. The setting is
indicated:
LED lit: coarse setting, LED
flashes: fine setting.
Press the Learn/Set button and
HI
keep it pressed.
After 5 s the switch point is
increased* (incremental by
pressing briefly or scrolling by
holding pressed).
HI
Indication:
The flashing LED moves from left
to right. After LED 9 has been
reached the cycle starts again at
LED 0. The LED which is constantly
lit moves on by one position.**
Press the Mode/Enter button
briefly (acknowledgement).
HI
The indication goes off briefly.
The setting becomes effective;
the unit passes into the operating
mode.