Soft starter 3RW402, 3RW403, 3RW404
Read and understand these instructions before installing, operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying
this device before working on this device.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
The terminals of the motor control device must not be touched when it is connected to a voltage in order to prevent electrical shocks or
burning. The output terminals of the motor control device are connected to a voltage even when it is in the OFF state.
Stand-alone installation spacings (see soft starter manual for side-by-side installation)
≥ 60 mm
[≥ 2.36 in]
1
5
3
1
a
4
6
2
≥ 40 mm
[≥ 1.56 in]
Setpoint values for motor current
Permitted setpoint values for the motor current, dependent on the CLASS setting at 40 °C surrounding air temperature
I
[A]
e
3RW4024-...
12.5
3RW4026-...
25.3
3RW4027-...
32.2
3RW4028-...
38
3RW4036-...
45
3RW4037-...
63
3RW4038-...
72
3RW4046-...
80
3RW4047-...
106
Programming the ON/RUN output 13/14 (factory setting: ON) (Fig. 3 in graphics section)
1. Start programming mode: (For the 3RW402 device, remove the cover as shown in Figure 2.) Press and hold the "RESET MODE" button (2) for
longer than 2 seconds until the LED "DEVICE" (5) flickers green. While pushing the "RESET MODE" button (2), press the "RESET/TEST" button
(1) for longer than 1 second until the LED "DEVICE" (5) on the device lights up red.
2. Display mode: LED "STATE/BYPASSED/FAILURE" (6) flashes green: ON mode. LED "STATE/BYPASSED/FAILURE" (6) flickers green: RUN
mode.
3. Change mode: Press the "RESET MODE" (2) button.
4. Exit programming mode and save settings: Press and hold the "RESET/TEST" button (1) for longer than 1 second until the LED "DEVICE" (5)
lights up green.
3ZX1012-0RW40-2DA1
CAUTION
Reliable functioning of
the equipment is only
ensured with certified
components.
NOTICE
Please adhere to the specified spacings when installing the device so that sufficient air can
circulate for ventilation. The unit is ventilated from bottom to top.
CAUTION
a
Risk of damage to property.
Ensure that no liquids, dust or conductive parts enter the soft starter.
NOTE
Surrounding air temperature - A rating assigned to open type equipment that refers to the
maximum ambient temperature of air immediately surrounding the equipment inside of the
ultimate enclosure.
a) 3RW402: 15 mm [0.59 in]
3RW403; 3RW404: 30 mm [1.18 in]
I
[A]
I
min
max
5
10.3
17.2
23
22.5
25.5
34.5
42.5
46
NOTE
This is a product for environment A. When used in a
household setting, this device can cause unwanted radio
interference. In this case the user may be required to carry
out appropriate measures to avoid such radio interference.
[A] CLASS 10
I
[A] CLASS 15
max
12.5
11
25.3
23
32.2
30
38
34
45
42
63
50
72
56
80
70
106
84
English
I
[A] CLASS 20
max
10
21
27
31
38
46
50
64
77
5