Safety precautions (continued)
CAUTION
Do not place a burning appliance in a place where
it is exposed directly to the air from the Lossnay
unit.
(It could cause an accident as a result of incomplete
combustion.)
Do not use at a place where it is exposed to high
temperatures (40˚C or higher), naked flames, or in
environment with combustible fumes.
(It could cause fire.)
Do not use in an environment such as a chemical
Prohibited
factory, where hazardous gases such as acidic
gases, alkaline gases, organic solvent fumes, paint
fumes, or gases containing corrosive components
are generated.
(It could malfunction.)
Do not install this product in a place where it is
exposed to ultraviolet light.
(UV may damage covering insulation.)
Put on gloves during installation.
(It could cause injury.)
Make sure the power supply isolator is turned off
on the power distribution panel when Lossnay
is not used for a long period of time after the
installation.
(It could cause electric shock, power leakage, or fire as
a result of deteriorated insulation.)
Always use the specified suspension bolts,
nuts and washers or correctly rated wire / chain
The instructions
hangers.
given must be
(Use of hardware with insufficient strength could result
followed.
in the product dropping.)
The outside ducts must be tilted at a gradient (1/30
or more) down toward the outdoor louvres from
Lossnay, and properly insulated.
(The entry of rain water may cause power leakage, fire,
or damage to household property.)
l When using the product where it is exposed to high temperatures
and humidity (40˚C or higher, RH 80% or higher), or where fog
occurs frequently, moisture is likely to condense in the core, and
may result in condensation build up in the unit. The product should
not be used under such conditions.
l Outdoor air may enter the Lossnay owing to the pressure
difference between indoor and outdoor or external winds even
when the product is not operated. It is recommended to install an
Electrically operated damper to block the outdoor air.
l In a cold weather area, an area with strong external winds or
where fog occurs frequently, cold outdoor air, external winds or fog
may be introduced into the product when its operation is stopped. It
is recommended to install an Electrically operated damper.
Eng-2
The control box cover must be closed after the
installation.
(Dust or humidity may cause power leakage or fire.)
When connecting external devices (electric heater,
damper, lamp, monitoring unit, etc.) using output
signals of the Lossnay unit, make sure to install
safety equipment for the external devices.
(It could cause fire, damage, etc. without safety
equipment.)
Select a duct heater in compliance with local and
national laws, ordinances, and standards.
Select a duct heater that has obtained the CE mark.
Install the duct heater separated from the product
by a distance of 2 m or more.
(Failure to do so may result in fire or equipment
damage due to the transmission of residual heat from
the heater.)
This appliance is not intended for use by persons
(including children) with reduced physical sensory
The instructions
or mental capabilities, or lack of experience
given must be
and knowledge, unless they have been given
followed.
supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they
do not play with the appliance.
(This appliance can be used by children aged
from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack
of experience and knowledge if they have been
given supervision or instruction concerning use
of the appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall
not be made by children without supervision.)
CAUTION
l When using the product in an environment where there is a
window, or opening near the outdoor louvre , where insects are
likely to gather around the interior or exterior light , take note that
small insects may intrude into the product.
l In a cold weather area, or others, dewing or freezing could occur
on the main unit, where the duct is connected, or other sections,
depending on the conditions of outdoor air and indoor temperature
and moisture, even if they are within the range of operating
conditions. Make sure to confirm the operating conditions and
other precautions, and do not use the product if dewing or freezing
is anticipated.
*Example of dewing condition - Outdoor air: -5˚C or lower, dew-
point temperature at installation place: 10˚C or higher (When the
indoor temperature is 22˚C or higher with the relative humidity
higher than 50%, or other)