Herunterladen Inhalt Inhalt Diese Seite drucken

Function Settings; Setting The Address - Mitsubishi Electric Lossnay LGH-200RVXT-E Installationsanleitung

Vorschau ausblenden Andere Handbücher für Lossnay LGH-200RVXT-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25

Function settings

Address setting is required when connecting to City Multi and MELANS.

Setting the address

Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Use a flat blade screwdriver to turn the address setting switch on
the circuit board.
• SA1 indicates the tens digit and SA2 indicates the ones digit.
• The factory setting is "00".
SA1
SA2
10s digit
1s digit
* When the address number has been changed, the data in the
memory is automatically reset.
Changing the function selection
switches (SW-2, 5 and 6)
Set the selection switches (SW-2 and 5) to perform the appropriate
function.
* All function except "Trial operation" and "Main unit setting" can be
set also from the remote controller (PZ-61DR-E). If the function is
switched later using the remote controller, it operates according to
the setting on the remote controller.
(SW2)
OFF
ON
1
Trial operation
2
No. 28
Pulse input setting
No. 63
External fan speed input setting (0 - 10 VDC)
3
4
No. 6
Indoor negative pressure setting
No. 7
Indoor positive pressure setting
5
No. 63
External fan speed input setting (0 - 10 VDC)
6
No. 51
Automatic ventilation mode setting
7
No. 57
Operation monitor output synchronized with exhaust fan or supply fan
8
No. 61
Fan speed for air volume "High" input
9
No. 62
Fan speed for air volume "Low" input
10
(SW5)
OFF
ON
No. 9
Delay start setting for air conditioner starting
1
No. 57
Operation monitor output synchronized with exhaust fan or supply fan
2
No. 13
,
No. 14
3
No. 5
Automatic recovery setting after power interruption
4
No. 1
Filter maintenance and fan power up setting against filter choking
5
No. 58
By-pass monitor output or Pre-heater output setting
6
No. 15
Interlock mode setting
7
No. 15
Interlock mode setting
8
No. 14
Exhaust fan setting at OA temperature lower than -15˚C
9
Main unit setting (refer to page 10)
10
Address setting switch
Exhaust fan setting
Change the function settings from the
remote controller PZ-61DR-E.
Please refer to the Instruction book of PZ-61DR-E for how to set the
function settings.
DIP-SW 6 is to idenify the model for PCB.
When replacing to new PCB, set the same
setting as old one.
(SW6)
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
* Do not change from factory setting.
If changed,please set as factory setting.
SW6-1 SW6-2 SW6-3 SW6-4
OFF
ON
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
ON
Eng-13

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Lossnay lgh-150rvxt-eLossnay lgh-250rvxt-e

Inhaltsverzeichnis