G
®
AERASGARD
RCO
The maintenance-free microprocessor-controlled AERASGARD
to detect the CO
content in air within a range of 0 ppm to 2000 ppm CO
2
The measurement signals from the CO
signals of 0 -10 V. Optionally, this CO
with display or switching output.
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment
for installation on vertically or horizontally installed in-wall flush boxes, with
pre determined breaking point for on-wall cable entry. or in enclosures made of
stainless steel (top and bottom part are of stainless steel, the lid is screwed on),
van dalism-secure version e.g. for schools, military barracks, and public buildings.
The CO
content in air is determined by a two-ray NDIR sensor (non-dispersive
2
infrared technology). The detection range of this CO
for standard applications such as monitoring of residential rooms or con ference
rooms. Room ventilation on an as-needed basis, improvement of well-being and
customer benefit, increased comfort as well as a reduction of operating costs by
energy conservation are only some of the beneficial results of employing
®
AERASGARD
RCO
sensors.
2
TECHNICAL DATA:
Power supply: .................................. 24 V AC ⁄ DC
Average power consumption: ....... < 3 VA at 24 V DC
CARBON DIOXIDE (CO
)
2
CO
sensor: ..................................... optical two-ray sensor (NDIR),
2
Measuring range, CO
: ................. multi-range switching
2
Output CO
: ..................................... 0 -10 V
2
Measuring accuracy CO
:............. ± 70 ppm plus 5 % of measured value
2
Pressure dependence: .................. ± 1.6 % ⁄ kPa (referred to standard pressure)
Long-term stability: ....................... ± 1 % of final value per year
Gas exchange: ................................. by diffusion
Warm-up time: ................................ ca. 1 hour
Ambient temperature: .................. +5 ...+40 °C
Electrical connection: .................... 0.14 - 1.5 mm
Enclosure: ........................................ plastic, material ABS,
Dimensions: ..................................... 98 x 106 x 32 mm (Frija II)
Installation: ...................................... wall mounting or on in-wall flush box, Ø 55 mm,
Protection class: ............................ III (according to EN 60 730)
Protection type: ............................. IP 30 (according to EN 60 529)
Standards: ....................................... CE-conformity, electromagnetic compatibility
2
transmitter are converted into standard
2
measuring transducer can be supplied
2
sensor is calibrated
2
non-dispersive infrared technology
(selectable via DIP switches)
0 ... 2000 ppm; 0 ... 5000 ppm; 0 ... 10000 ppm
2
, via terminals on circuit board
colour pure white (similar RAL 9010),
stainless steel enclosure optional
100 x 100 x 25 mm (stainless steel enclosure)
base with 4-hole for mounting on vertically
or horizontally installed in-wall flush boxes for
cable entry from the back, with predetermined
breaking point for on-wall cable entry from
top ⁄ bottom in case of plain on-wall installation
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 73 ⁄ 23 ⁄ EEC
®
RCO
is used
2
Connecting diagram
.
2
Connecting diagram
Schematic diagram
CO
1
UB+ 24V AC/DC
2
UB- 24V AC/DC
3
Free
4
Free
5
GND
6
Free
7
Free
Output CO
content in ppm 0-10V
8
2
1
UB- GND
2
UB+ supply voltage 24V AC/DC
3
Output CO
content in ppm 0-10V
2
CO
Sensor
2
4
3
2
range
2
ON
1 2 3 4
RCO
2
RCO
- Display
2
RCO
- Display
2
CO
range
2
ON
1 2 3 4
1
ATM
Atmospheric
pressure
sensor