Herunterladen Inhalt Inhalt Diese Seite drucken

DAB AD x.x AC series Installations- Und Wartungsanleitungen Seite 76

Für drehstrompumpen
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 199
Inverter power
supply
Inverter output
Mechanical
specifications
Installation
Control and
operating
hydraulic
specifications
Sensors
Functions and
safety devices
Technical specifications
Voltage [VAC]
(Tol +10/-20%)
Phases
Frequency [Hz]
Current [A]
Leakage current to earth
[ma]
Voltage [VAC]
Phases
Frequency [Hz]
Current [A rms]
Minimum current [A rms]
Max. power output [kW]
Mechanical power P2
Unit weight [kg]
(excluding packaging)
Package weight [kg]
Maximum dimensions
[mm](WxHxD)
Work position
IP protection rating
Max. ambient temperature
[°C]
Max. section of lead
accepted by input and output
terminals [mm²]
Min. diameter of cable
accepted by input and output
cable glands [mm]
Max. diameter of cable
accepted by input and output
cable glands [mm]
Pressure regulation range
[bar]
Options
Type of pressure sensors
Pressure sensor full scale
[bar]
Type of flow sensor
supported
Connectivity
Safety devices
Table 1: Technical specifications
ENGLISH
AD 15.0 AD AD 11.0 AC
380-480
3
50/60
55-44
<7,5
0 - V alim.
3
0-200
41,0
2
22,0
20 CV / 15 kW
1 – 95% full scale without press.
Ratiometric (0-5V) / 4:20 mA
Serial interface
Multi inverter connection
Dry running
Current sensitivity on output phases
Temperature overload on internal electronics
Abnormal power supply voltages
Direct shorting between output phases
Fault on pressure sensor
74
AD 7.5 AC
380-480
3
50/60
42-33
<7,5
0 - V alim.
3
0-200
31,0
2
16,0
15 CV / 11 Kw
10 CV / 7,5 kW
16,4
19,8
265x390x228
Any
20
50
16
18
25
Flow sensor
16 / 25 / 40
5 pulses [Vpp]
380-480
3
50/60
29,5-23,5
<7,5
0 - V alim.
3
0-200
22,0
2
11,0