Connect the regulator using RS485 bus to PC with installed configuration software domat.exe
Switch INIT to ON
Connect the power supply (use exclusively the black connector on the bottom of the regulator
Search for the regulator by the software (Scan function)
Switch INIT to OFF
Click to the regulator in the domat.exe software
Click to the INIT button in the domat.exe software
Turn the power supply off and back on
8
9
Rear side of regulator board:
BUS END: switch on if the regulator is the last on the
USR(1): Chooses the valid temperature sensor:
INIT(2):
1: K-
RS 485 communication -
2: K+
RS 485 communication+
3: DO1
output heating, 1st stage
4: N/C
not used
5: DO2
output heating, 2nd stage
6: -
Power supply – pole, reference
7: +
Power supply + pole
8: AIN
external temperature sensor Pt1000
9: AGND
external temperature sensor Pt1000
RS485 bus
● OFF - internal temperature sensor
● ON - external temperature sensor (Pt1000)
sets the default communication settings:
address 1, transfer rate 9600bps