Error codes

5
Error codes
Problem
The display shows
„Error G1"
The display shows
„00001"
The display shows
„00002"
The display shows
„00003"
The display shows
„00004"
The display shows
„00005"
16
Cause
A connection to the analysis
module could not be made.
The readings are unstable.
The readings are excessively
high.
Calibration with the ambient
air failed.
The device is operating
outside the recommended
temperature range.
The refrigerant sample has a
very high content of air or the
amount of refrigerant was too
low for testing.
ASC5300G
Remedy
Check the connections.
Are the LEDs on the module
activated?
Keep possible electrical
sources of interference, such
as mobile phones or welding
equipment, away from the
device.
Keep possible electrical
sources of interference, such
as mobile phones or welding
equipment, away from the
device.
Ensure the device is
adequately ventilated.
Leave any leaking refriger-
ant to drain off.
Only use the device in tem-
perature-controlled rooms
(10 °C – 45 °C).
Ensure sufficient ventilation.
Make sure that there is
enough refrigerant pressure.
Make sure that all the hoses
are connected, not kinked
and free of oil.
EN