G1506S
EVALUATION UNIT

11. Technical data

G1506S
Active ClassicLine module
AS-i interface to FC/FC-E
lower parts
Sockets M12 x 1
AS-i version 2.1
IR addressing possible
category 4 to EN 954-1
For the connection of 1 chain
with up to 8 fail-safe switches
Electrical design
Operating voltage
Current consumption
Enable condition
Power-on delay time
Response time (also see page 18)
Operating mode
Input fail-safe switches
Sensor supply
Voltage range
Short-circuit protection
Reverse polarity /
overload protection
Switching output
Galvanically decoupled /
short-circuit protection
Current rating
External supply
Voltage range
• = yes
20
PAGE
90
ERROR
I-1
O-3
AUX
M12 1DI 1DO T IP67
1 safe input / 1 unsafe output
26.5...31.6 V DC *)
Input signal of the connected fail-safe switches delayed
by 0.18 ... 16 ms
5 s (Power On), 1 s (normal operation) for enabling
respectively without power-on delay time
of the connected fail-safe switches.
Permanent operation
19,2...30 V DC via flat cable
500 mA, PNP switching
to EN 50106 (PELV) via FC-E coupling module
24 V DC (15...30 V DC) via flat cable
FAULT
PWR
< 250 mA
< 220 ms
via AS-i supply
pulsed
– / •
• / •
46,5
24