Draining the water coil (W)
The drain valves are on the underside of the coil on the
connector side. It can be accessed via the front hatch.
Trouble shooting
If the fans are not working or do not blow properly, check
the following:
That the intake grille/filter is not dirty.
Functions and settings of the control system PLS, see
manual for PLS.
If there is no heat, check the following:
Functions and settings of the control system PLS, see
manual for PLS.
For units with electrical heating, also check the following:
Power supply to electric heater coil; check fuses and
circuit-breaker (if any).
That the overheat protection for the motors has not been
deployed.
For units with water coil, also check the following:
That the water coil is air free.
That there is enough water flow.
That incoming water is heated enough.
If the fault cannot be rectified, please contact a qualified
service technician.
Residual current circuit breaker (E)
When the installation is protected by means of a residual
current circuit breaker, which trips when the appliance
is connected, this may be due to moisture in the heating
element. When an appliance containing a heater element
has not been used for a long period or stored in a damp
environment, moisture can enter the element.
This should not be seen as a fault, but is simply recti-
fied by connecting the appliance to the main supply via
a socket without a safety cut-out, so that the moisture
can be eliminated from the element. The drying time
can vary from a few hours to a few days. As a preventive
measure, the unit should occasionally be run for a short
time when it is not being used for extended periods of
time.