DATA SHEET
Technical Specification:
•
2 metre connecting cable
•
3 metre float switch cable
•
Self-priming
•
3 metre suction lift
•
12 metre discharge head
•
Pumps water/fibrously
contaminated water and air
•
Water pumping capacity 6.25 litres per
hour @ 12m discharge
•
Pump has a selector switch for manual
flushing
•
Temperature limits on pump head tube:
0°C to +100°C
•
Pump rating 0.2A, 230V AC
Dimensions:
Height: 142mm Width: 160mm
Depth: 83mm Weight: 1.4kg
Electrical Connections:
Brown:
Live
Blue:
Neutral
Green/yellow:
Earth
DESIGNED BY ENGINEERS
FOR ENGINEERS
The Aspen Mechanical Pump
Suitable for applications where condense tray allows for easy
positioning of float mechanism.
Description:
The pump is designed to be fitted in the ceiling void and to lift condensated water where
a gravity drain is too obtrusive. It can be used on cassettes fitted with an internal lift
pump.
Installation Notes:
This pump is designed to sit level on its
base and must at all times have adequate
space around it for good ventilation.
Ensure that there are no kinks or trapped
parts in the piping, which must have an
inside diameter of 6mm and an outside
diameter of 9mm.
Fix the pipes with cable ties to the pump
inlet and outlet.
TEST
PUMP
MOTOR
PUMP CASING
Service Guide:
1
Inspect the pump head regularly and change the pump head tube every 12 months or
more often if required. If any problems with the pump occur check the tube first!
2
To remove the pump head, make sure the roller assembly is vertical. Remove screws
and fit the replacement pipe. The addition of a smear of silicon grease will ease
refitting the lid and reduce potential friction noise.
3
The test switch should always be returned to the "RUN" position after testing.
4
Replacement pump head tubes and other accessories can be obtained from the
manufacturers. Please quote the serial number (to be found on the pump) when
ordering spare parts.
5
The float chamber should be cleaned annually.
For further help contact Aspen Pumps:
Aspen Pumps Apex Way Hailsham East Sussex BN27 3WA www.aspenpumps.com
Tel: +44 (0)1323 848842 Fax: +44 (0)1323 848846 sales@aspenpumps.com
Decide which reservoir is correct for your
installation. Ensure you have placed float
magnet facing upwards. Connect the
water reservoir to the water drain of
evaporator or if using other reservoir place
and fix into condensate tray. Ensure
reservoir is mounted horizontally.
NORMAL
PCB
LIVE
NEUTRAL
EARTH
FLOAT