Installation method (continued)
When take Malfunction monitor output, or take Bypass
5
operation monitor output.
Bypass operation indicator
Monitor output terminal
Power
Supply
Lamp or
monitoring unit
Malfunction indicator
Connect to 6 and 7, or 7 and 8 of the monitor output terminal
block (TM3) with reference to the wire connection diagram.
Note
* Don't tighten screws of terminal block with a torque larger than
0.5Nm. It could damage the PCB.
Bypass or Delay 2 monitor output with delay function 2 can be
possible. (Refer to function settings
When connect to an Electrically operated damper, or take
6
Operation monitor output
Connect the power supply cable from the Electrically operated
damper to 9 and 0 of the monitor output terminal block (TM4)
with reference to the wire connection diagram.
Operation monitor output with delay function 1 can be possible.
(Refer to function settings
6
Power Supply
Monitor output
terminal (TM4)
Electrically 
operated
damper
Lamp
Note
* Don't tighten screws of terminal block with a torque
larger than 0.5Nm. It could damage the PCB.
* Response times to external input signals
are as shown in the following table.
When switching High/Low fan speed externally
7
(when CO
sensor or other equipment is connected)
2
Using marketed CO
sensor, etc., make connection by inserting
2
the optional remote ON/OFF adaptor (PAC-SA88HA-E) in the
connector CN16 (High/Low selector) as shown by the figure.
n To force High fan speed externally
CO
sensor, etc.
Remote ON/OFF adaptor
2
(When CO
increases: Closed)
(Optional) PAC-SA88HA-E
2
SW1
SW1: High fan speed operation switch
Not used. Insulate completely.
(When closed: For High fan speed operation)
Max wiring length 10 m
When SW1 is "ON", fan speed of the Lossnay will be set to "High"
(Extra-High) regardless of the remote control setting.
Use this in such a way that it ventilates at Low fan speed normally,
and when the external sensor detects contamination of indoor air,
it changes to High (Extra High) fan speed operation.
n To force Low fan speed externally
CO
sensor, etc.
Remote ON/OFF adaptor
2
(When CO
decreases: Closed)
(Optional) PAC-SA88HA-E
2
SW1
SW1: Low fan speed operation switch
Not used. Insulate completely.
(When closed: For Low fan speed operation)
Max wiring length 10 m
When SW1 is "ON", fan speed of the Lossnay will be set to "Low"
regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed
normally, and when the external sensor detect that the indoor air
contamination is low, it changes to Low fan speed operation.
Bypass operation signal
TM3
contactor rating
6
Max 240 VAC,
1 A
24 VDC,
1 A
7
Min
220 VAC,
100 mA
5 VDC,
100 mA
8
Malfunction signal
"Setting for TM3 67")
13
"Setting for TM4 90")
0
9
Contactor rating
Max 240 VAC, 2 A
24 VDC, 2 A
Min 220 VAC, 100 mA
5 VDC,
100 mA
External Signal Response Time
Level Signal
Max. 7 sec.
Pulse Signal
Max. 200 msec
Lossnay
control board
Brown 1
CN16
Red 2
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Lossnay
control board
Brown 1
Red 2
CN16
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
8
When switching Bypass externally.
Establish the wire connection by inserting the optional remote ON/
OFF adaptor (PAC-SA88HA-E) in the connector CN16 (Ventilation
mode selector).
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
SW1
Not used. Insulate completely.
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
Max wiring length 10 m
With SW1 is "ON", the ventilation mode of Lossnay is changed to the
Bypass ventilation regardless of the setting on the remote controller.
* When the outdoor air temperature drops lower than 8˚C, it
changes to the heat exchanger ventilation. (Display of the
remote controller does not change.)
When using the remote/local switching and the ON/OFF
9
input (level signal)
The remote controller (PZ-41SLB-E) cannot be used.
Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in
CN32 on the Lossnay control PCB.
Remote control
board
Relay circuit
SW2
X
X
SW1
Y
Y
SW1: When this is ON, Lossnay cannot turn ON/OFF by the
Remote Controller (PZ-60DR-E, PZ-52SF-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting
SW2 at ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
When connecting to the City Multi, Lossnay remote controller (PZ-52SF-
10
E) or Mitsubishi Electric Air-Conditioner Network System (MELANS)
* If centralized control is performed according the wire
connection shown in this section, the remote controller (PZ-
41SLB-E) cannot be used.
M-NET transmission cable input terminal block
• One shielded wire is connected to TB5 S on the PCB on terminal.
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the City Multi indoor unit, or
Mitsubishi Electric Air-Conditioner Network
System (MELANS) - to the Lossnay.
• Connecting positions are different for the Remote Controller
PZ-60DR-E and PZ-52SF-E.
PZ-60DR-E:
Connect to TM4 1, 2 on the PCB. (See Section
connecting with Remote Controller (PZ-60DR-E)".)
PZ-52SF-E:
Connect to TB5 A, B on the same terminal block as for the
M-NET transmission wires.
• Securely connect the M-NET transmission wires to TB5 AB.
(No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm
to 2.0 mm
2
Lossnay
control board
Brown 1
Red 2
CN16
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Remote ON/OFF adaptor
Lossnay
(Optional) PAC-SE55RA-E
control board
Orange 1
CN32
Red 2
Brown 3
Max wiring length 10 m
TB5
A
B
S
Shielded wire
M-NET transmission cable
"When
1
2
19