AFRISO CapFox ENT 7 Betriebsanleitung Seite 48

Kompakter kapazitiver füllstandgrenzschalter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6.2
Relay output
DAMAGE TO THE PRODUCT
Electrical systems may be impacted and the switching contact may be destroyed
by voltage peaks when inductive consumers are switched off.
Verify that you use commercially available standard RC combinations such
as 0.1 µF/100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.
Electrical connection
NOTICE
A
A. Voltage-free changeover contact
1. Route the permanently installed
cable into the control unit through
the cable gland at the right.
2. Connect the cable to the three ter-
minals at the right (changeover
contact).
During normal operation, the relay is
energised; it is de-energised when
the adjusted limit value is reached or
in the case of power outage.
CapFox® ENT 7
EN
20