Balluff BAE0008 Typ BAE PS-XA-3Y-24-100-006 Betriebsanleitung Seite 2

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical Data
Installation and Operating
Din Rail Mountable
Switching Power Supply
BAE0008
Ordering Code
BAE PS-XA-3Y-24-100-006
Part Number
Safety notes
Read Instructions!
Before working with this unit, read these instructions
carefully and completely. Make sure that you have
understood all the information!
Disconnect system from supply network
Before any installation, maintenance or modification work:
Disconnect your system from the supply network. Ensure that
cannot be re-connected inadvertently!
Before start of operation
Ensure appropriate installation
Warning! Improper installation / operation impair safety and
result in operational difficulties or complete failure of the unit.
The unit must be installed and put into service appropriately
by qualified personnel. Compliance with the
relevant regulations must be ensured. Before operation is
begun the following conditions must be ensured, in particular:
Connection to main power supply in compliance with
VDE01000 and EN50178.
With stranded wires: all strands must be secured in the
terminal blocks (potential danger of short circuit).
Unit and power supply cables must be properly fused; if
necessary a manually controlled disconnecting element must
be used to disengage from supply mains.
The non-fused earth conductor must be connected to the
"
" terminal (protection class 1).
All output lines must be rated for the power supply output
current and must be connected with the correct polarity.
Sufficient air-cooling must be ensured.
Use in a pollution degree 2 environment.
In operation: No modifications!
As long as the unit is in operation: do not modify the
installation! The same applies also to the secondary side. Risk
of electric arcs and electric shock (fatal)!
Only (dis) connect plug connectors when
the power is off!
Convection cooling
Do not cover
any ventilation holes!
Leave sufficient space
around the unit
for cooling!
See supplementary sheet "Technical Data" and Fig. 1
Warning: High voltage! Store energy!
The unit contains unprotected conductors carrying a lethal
high voltage, and components storing substantial amounts of
energy. Improper handling may result in an electric shock or
serious burn!
The unit must not be opened except appropriately trained
personnel!
Do not introduce any object into the unit!
Keep away from fire and water!
Fig. 1
In-
Out-
put
put
Fig. 2
Balluff GmbH
Schurwaldstraße 9
73765 Neuhausen a.d.F.
Germany
Fon +49 7158 173-0
Fax +49 7158 5010
balluff@balluff.de
www.balluff.com
Installation
Application
This unit is a primary switched-mode power supply designed
for use in panel-board installations or building-in
applications
where access to the supply is restricted (shock-
hazard protection). It must only be installed and put into
service appropriately by qualified personnel.
Mounting
Mounting
Permissible mounting position: see Fig. 1 keep free ventilation
hole, leave space for cooling! Recommended to have 25mm
free space at all sides for ventilation / cooling:
see supplementary sheet "Technical Data".
Snap on support rail
(See Fig. 2)
Tilt the unit slightly rearwards.
Fit the unit over top hat rail.
Slide it downward until it hits the stop.
Press against the bottom front side for locking.
Shake the unit slightly to check the locking action.
Front elements
Operation indicator
Indicates whether the unit is working properly. Green LED is
lit on if the voltage at the output terminal is more than 75 %.
DC output low indicator
Red LED lighten up while the voltage at the output terminal
is 70 % to 90 % of the rated.
Potentiometer
Setting the output voltage.
Connection / Internal fuse
Connection
Data for permitted loads, cable cross-sections and stripping:
see enclosed leaflet " Technical Data " (See Fig. 3).
Use only commercial cables designed for the indicated
voltage and current values!
With flexible cables: make sure that all stranded cable are
secured in the terminal.
Ensure proper polarity at output terminals!
Grounding
Do not operate without PE connection!
EMC and safety standards (CE mark, approvals), the unit
must only be operated if the PE terminal
the non-fused earth conductor.
Secondary side is not earthed; if necessary the
terminal can be earthed optionally.
Internal fuse
The internal input fuse serves to protect the unit and must
not be replaced by the user. In case of an internal defect, the
unit must be returned to the manufacturer for safety reasons.
External circuit breaker
For input line protection observe national regulations;
recommended circuit breaker: Mitsubishi, Type NF30-CS,
rated 20A max or equipollent of TUV/VDE/UL approved
sources.
Removal
Removal from DIN Rail
Insert a flat screwdriver into the slot in the clamp. Pull down
the clamp out unit the clamp clicks, and turn the switching
power supply bottom out. (See Fig. 4)
Fig. 3
Connector size range:
AWG24 - 10 / 0,25 - 4 mm²
- Input connector can withstand torque at maximum
9 pound-inches
- Output connector can withstand torque at maximum
5.5 pound-inches
Use copper conductors only 60 / 75'C
Max. surrounding air temperature of 50 °C for UL 508
Fig. 4
Technical
Data
Ordering Code
Part Number
General
Switching frequency
Isolation voltage
Isolation resistance ..........................................
Power up delay
Ambient temperature
Derating
.........................................................
Storage temperature
Relative humidity
..........................................................
Cooling
Dimension (W x L x D)
............................................................
Weight
Input specifications
Input voltage
Input voltage range
Rated input current ........................................... 0.85 A at 380 VAC / 0.7 A at 500 VAC
Inrush current
Line frequency
......................................................
Input fuse
Output specifications
Output voltage
Output current ..................................... 10 Amps
Output wattage
Voltage trim range
Output voltage accuracy
Line regulation
Load regulation
Settling time
Temperature coefficient ...................... ± 0.02 % / °C
Ripple & noise
Hold up time
DC ON Indicator
DC LOW Indicator
Parallel modus .................................... Parallel function available (switch)
Efficiency ............................................ 91 %
Rated over load protection ................. 120 ~ 140 %
Over temperature
Output short circuit
To comply with
is connected to
Approval and standards
UL / cUL .......................................
or
TÜV .............................................
CE ...............................................
Fig. 5 Derating
100
75
0
-25
Temperature [ C ]
8 mm
All specifications are typical at nominal line voltage,
full load, 25°C. Unless otherwise noted
BAE0008
BAE PS-XA-3Y-24-100-006
.......................................
> 100 kHz
.............................................
3.000 VAC
100 MΩ
..............................................
< 1 s
......................................
-25 °C ~ +71 °C
-2.5 % / °C from +61 °C
.......................................
-25 °C ~ +85 °C
............................................
20 ~ 95 % RH
Free air convection
....................................
89.0 x 124.0 x 112.0 mm
1.1 kg
.................................................
3 x 340 ~ 575 VAC
........................................
340 ~ 575 VAC / 480 ~ 820 VDC
................................................
< 20 A
...............................................
47 ~ 63 Hz
2 A / 600 VAC internal / phase
..................................
24 VDC
.................................
240 WATTS
.............................
22.5 ~ 28.5 VDC
....................
-0 %, +1 %
..................................
± 1 %
.................................
single mode ± 1 %, parallel mode ± 5 %
......................................
1 ms
..................................
100 mV
.....................................
> 20 ms
...............................
Green LED
............................
Red LED
.............................
100 ~ 110°C, detect on heatsink, shut down O/P voltage,
recovers automatically after temperature goes down
...........................
Current limited
UL 508 Listed , UL 60950-1
EN 60950-1
EN 55022 & EN 61000-6-3, EN 61000-3-2,
EN 61000-3-3, EN 55024 & EN 61000-6-2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8,
EN 61000-4-11, EN 61204-3