MEANINGS OF THE LEDS
BLUE
STATUS
Unit OFF
LED
NETWORK
OC Master
LED
Looking at the I/O board from the front, the
STATUS LED is on the left, while the NETWORK
LED is on the right.

TECHNICAL DATA

Power supply
230Vac 50/60Hz
Power 2.5 W
Operating
Range 0-50°C
Temperature
Storage Temperature
Range -10-60°C
IP protection rating
IP30 (user unit)
Type of board
Type 1.C
Output relay
Normal Open 5A @ 240V (Resistive)
Max room temperature: 105°C
Micro-interruption
Inputs
NTC Temperature Probes
0-5V probes on
Dry contacts (digital inputs)
Temperature Probes
NTC probes 10K Ohm @25°C
Range -25-100°C
Humidity probe
Resistive type of probe
Range 20-90%RH
Max cable section for
1.5 mm
clamps
Pollution rating
Degree II
Heat/fire resistance
Category D
Over-voltage category Category II
EMC conformity
EN 61000-6-1(2007)
standards
EN 61000-6-3(2007) + A1(2011)
FC66003946
Rev 00
Controller for units
GREEN
RED
Alarm in
Unit ON
progress
Communication
No
OK
communication
2
It is strictly forbidden to reproduce this manual, even partially

INSTALLATION AND MAINTENANCE

The procedures for installing the user interface, the power
board and probes, with specific instructions for individual
hydronic units of the Daikin range, will be described at a
later stage.

PROBE INSTALLATION

The FWECSA controller manages the following probes:
Air temperature reading probe installed inside the
user unit; it does not require any special installation
operations.
Probe (optional and alternative to the previous one)
connected to the I/O board for temperature readings of
the air taken in by the machine, or in any other point of
the room subject to temperature adjustment (REMOTE
AIR PROBE)
Probes (optional) for water temperature readings: it is
possible to connect one or two probes, depending on
whether the unit is connected to a 2- or 4-pipe system.
Probe (optional) to read the relative ambient humidity,
connected to the I/O board
To avoid interference, and subsequent faulty
operation, the probe cables must NOT be set
up near power cables 8230V).

REMOTE AIR PROBE INSTALLATION

Use of the remote air probe to adjust the room temperature
is optional. When it is used, it becomes the main adjustment
probe, in place of the probe installed inside the user unit. It
is always possible to choose the main room temperature
adjustment probe from the "air probe" parameter contained
in the CONFIGURATION MENU.
The remote air probe must always be connected to clamps
I1-C1 on the I/O board.
USER MANUAL
EN
20