Herunterladen Diese Seite drucken

ENAG CDS3/24-150-TRI Bedienungsanleitung Seite 30

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 32
Remote LEDs accessory : reference LED-DEP-CDS3
Allows having at distance the charger LED: ON/BOOST, absorption/Floating.
A 5-metre cable to connect on KLD123.
Power-sharing function (K19 connector)
Allows to balance the voltage and current regulation, when chargers are mounted into parallel (up to 6
chargers : 1 master + 5 slaves).
This function can be done by connecting a specific cable (can be ordered on option) on K19 connector of the
parallel-mounted chargers.
This function can only operate if :
• The chargers have the same size (voltage and current)
• The chargers have the same settings (RC1 and SW1)
Mounting of 2 chargers into parallel :
L1 /
Entrée AC
AC input
Longueurs et sections de câble identiques
pour les liaisons L1 à L4.
Same length and cable section
for links L1 to L4.
L2 /
Liaison Power Sharing (K19)
Power Sharing Link (K19)
L3 /
Entrée AC
AC input
20-07-09 N°10350 27A
L4 /
28

Werbung

loading