System messages
The following messages must be acknowledged with the
function.
Message
Function
COM
comerr
ADDR
dbladd
Parameter
Echo
Memory (copy)
empty
Data, Parameter
error
ADDR
found
ASI V =
hiload
ASI V =
lobatt
ASI V =
intern
ADDR, Profile, Data,
master
Parameter, Memory
ADDR
no asi
Data
no out
Data
no inp
Para
nopara
Memory (copy)
notequ
ASI V=
ol.
ASI V=
-pol
ADDR, Profile, Data,
prgerr
Parameter, Memory
Data, Para, Memory (copy)
Prog
ADDR, Profile, Data,
read
Parameter, Memory
ADDR, Data
search
Data
ualbit
Data, Profile
usenot
Memory (copy)
useone
3RK1703-2WB02-1CA1
key to return to the currently selected
Significance
Transmission error
Same address occurs twice (doublet)
Received parameter XH
Entire system has been copied
Address 0: Data and parameters cannot be read
Slave addresses recognized
Current load too high for addressing device
Battery can no longer supply full AS-i voltage
No AS-i power pack on bus
Active master on bus
Can't find any slave addresses
This slave type has no outputs
This slave type has no inputs
Can't find parameters
Can't find suitable slave profile
Overload: U
> 35 V
AS-i
Voltage < -2 V (-pol blinks)
Programming error
Transferring data to the slave
Reading data
Searching for slave addresses
Faulty valid bit
Address 0 not allowed
Only 1 slave can be copied, use addressing plug
17