Herunterladen Inhalt Inhalt Diese Seite drucken

Adjusting The Boiler To The System; Changing Parameters At User Level (Without Access Code) - REMEHA GAS 210 ECO PRO Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für GAS 210 ECO PRO:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

GAS 210 ECO PRO

3.3 Adjusting the boiler to the system

2x
2x
114492LTAL21H021b
fig. 03
Changing parameters
114500-090211
• Press the [+] key again until pr appears alternating and, for
example, 3.0 bar, the actual water pressure (if no water pres-
sure sensor is connected, --.- bar appears);
• Press the [+] key again until p appears and, for example,
78 %, the actual modulation percentage;
• Press the [+] key again, the read-out cycle starts again with
5t, etc;
• Press the
key twice to return to the display with the
current operating status.
The boiler's control unit is set to the most common central heating
systems. With these settings, practically all central heating sys-
tems will work well. However, the user or the installer can optimise
the parameters as he/she wishes.
3.3.1 Changing parameters at user level (without
access code)
The following settings can be changed at user level:
p1 = Maximum flow temperature [°C], adjustable between
20 and 90°C;
p 2 = Pump post-circulation time 0..98 mins, 99 is continuous;
p 3 = Boiler control; central heating on/off.
0 = Central heating
1 = Central heating
p4 = Display
0 = Simple display
1 = Comprehensive display
2 = Display automatically goes to simple after
three minutes (factory setting)
The parameters can be changed at user level as follows:
1. Press the  -key several times until the   s ymbol flashes in
the menu bar;
2. Select the users menu using the  -key, p1 appears (the
1 flashes);
3. Press the [+] -key; p2 appears (the 2 flashes);
4. Press the   - key again; 3 (min) appears and flashes: (factory
setting);
5. Change the value by pressing the [-] -key or the [+] -key, in this
case for example to 15 min, with the [-] -key;
6. Confirm the value with the  -key, p2 appears (the 2 fla-
shes);
-
7. Press
t he
key twice, the boiler enters the current opera-
ting status.
The p1 to p4 settings can be changed in the same way as
p2.
off
(= factory setting)
on
3. Control
27

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis