Herunterladen Inhalt Inhalt Diese Seite drucken

Erweiterung Umg96 Rm-Pn; Parameter - janitza UMG 96RM Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für UMG 96RM:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Modbus-Adressenliste

Erweiterung UMG96 RM-PN

Weiterführende Parameter und Adressenliste zu der
Erweiterung UMG96RM-PN
Adresse Format
RD/WR

Parameter

Adresse Format
RD/WR
520
SHORT
RD/WR
521
SHORT
RD/WR
524
SHORT
RD/WR
525
SHORT
RD/WR
526
SHORT
RD/WR
527
SHORT
RD/WR
528
SHORT
RD/WR
530
FLOAT
RD/WR
532
FLOAT
RD/WR
534
FLOAT
RD/WR
536
FLOAT
RD/WR
538
FLOAT
RD/WR
540
FLOAT
RD/WR
542
SHORT
RD/WR
543
SHORT
RD/WR
544
FLOAT
RD/WR
546
FLOAT
RD/WR
548
SHORT
RD/WR
549
SHORT
RD/WR
550
SHORT
RD/WR
551
SHORT
RD/WR
552
SHORT
RD/WR
553
SHORT
RD/WR
554
SHORT
RD/WR
20010
UINT
20012
UINT
20014
UINT
UMG 96RM
78
Einheit
Bemerkung
Einheit
Bemerkung
Modbus Timeout: Time (in ms) after
a Modbus request over the module is
discarded to the base
Changeover of the digital IOs of the module
0=output, 1=input
Inverting digital output 3
Inverting digital output 4
Inverting digital output 5
Digital out 1, source Profinet: Source for
base outputs (selection by Addr. 200 = 5)
Digital out 2, source Profinet: Source for
base outputs (selection by Addr. 202 = 5)
I4, current transformer, primary
I4, current transformer, secondary
I5, current transformer, primary
I5, current transformer, secondary
I6, current transformer, primary
I6, current transformer, secondary
Type I5: 0=residual current, 1=temperature
Type I6: 0=residual current, 1=temperature
Temperature offset, Temp1
Temperature offset, Temp2
Temperature sensor, Temp1
(0=PT100, 1=PT1000, 2=KTY83, 3=KTY84,
4=resistor in ohm)
Temperature sensor, Temp2
(0=PT100, 1=PT1000, 2=KTY83, 3=KTY84,
4=resistor in ohm)
Tariff configuration input 1; if Input 1 is set,
configurable counters are set in tariff 1 *
Tariff configuration input 2; if Input 2 is set,
configurable counters are set in tariff 2 *
Tariff configuration input 3; if Input 3 is set,
configurable counters are set in tariff 3 *
Enable transformer connection ckeck channel I5
Enable transformer connection ckeck channel I6
Device IP address
Device netmask
Device gateway IP address
Index
Einstellbereich
Voreinstellung
0-10000
200
0, 1
0
0, 1
0
0, 1
0
0, 1
0
0, 1
0
0, 1
0
0-1000000
5
1.0-5.0
5
0.0-1000000.0
1
1.0-5.0
1
0.0-1000000.0
1
1.0-5.0
1
0, 1
0
0, 1
0
-1000.0 - 1000.0
0
-1000.0 - 1000.0
0
0-4
0
0-4
0
0-127
0
0-127
0
0-127
0
0,1
0
0,1
0
0, 0xFFFFFFFF
0xA0A0AC8
(10.10.10.200)
0, 0xFFFFFFFF
0xFFFFFF00
(255.255.255.0)
0, 0xFFFFFFFF
0xA0A0A01
(10.10.10.1)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis