Herunterladen Inhalt Inhalt Diese Seite drucken

The Remote Control Rcc-01; The Temperature Sensor Ct-35 - Aeca Steca Compact C 1600-12 Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Steca
In factory we program this for a dysfunction alarm. The contact is active when one of
these situations is detected:
− Over temperature (LED 10 lit)
− Overload (LED 11 lit)
− Over or less voltage of batteries (LED 12 lit or blinking)
− COMPACT is turned off manually or with a fault (LED 13 lit)
In case this function is not wished, it must be modified by programming according to
procedure in chap. 5.4.

4.09 The Remote Control RCC-01

As an option, a Remote
Control can be connected to
the COMPACT. All operating
controls and displays except
from level adjustment are
available
on
the
Control. The Remote Control
is supplied with a 20m long
cable. It can as long as 40m.
The Remote Control is sui-
table for surface mounting on
the wall or on to a switch
board. It is fixed with 4
screws. The COMPACT can
also be programmed with the
Remote
Control.
Programming is descry-bed in
the section „Programming".
The output power and the charging currents are displayed on the Remote Control.
In the Remote Control there is an additional Alarm Contact and a built-in Control
Input. These two functions are available through Tip-jack RJ11/4 for use. This
Auxiliary Contact is Front / Work Contact (max. 0.5A!), which is independent from the
Auxiliary
Contact
COMPACT. This con-tact is
active in case of an alarm of
the COMPACT.
The Control Input is connected
in parallel to the ON/OFF-
push button. The COMPACT
can be switched on or off
through this input with an
impulse button or an impulse
contact.
Caution: No external voltage
should be connected to this
Input Control.
Order Number for Remote Control: RCC-01
Dimensions: H x B x T / 111.5 x 136.5 x 25mm

4.10 The Temperature sensor CT-35

Remote
The
of
the
COMPACT V6.4
COMPACT
21/56