4.7.1 Set the transfer voltage threshold
The voltage threshold of the transfer can be adjusted between 150 to 230V with the
turning knobs (23). From factory this value is 200V. Most appliances can work on this
voltage. When the Input voltages reach the selected value on turning knob, the
inverter switches off and the AC INPUT goes directly on the AC OUTPUT. When the
voltage INPUT is less of 20V the value set, the transfer is stopped and the OUTPUT
switches back on the inverter.
Note : Don't use the turning knobs "TRANSFER" (23) to adjust the AC OUTPUT
voltage ! This is only it's only a voltage threshold level to enable or disable the
transfer.
4.7.2 FAST (UPS)- MODE for the Transfer Switch
The quick and break free Transfer mode is programmed with a slide switch „Transfer
Delay" OFF, which is on the front side (cable connections side).
The aim of the COMPACT is to supply the appliance with a break-free alternating
voltage. When the incoming voltage AC IN no longer matches values which have
been set with the Turning Knob 23, the inverter switches on at once. The transfer is
carried out in 0.02 seconds. This quick transfer ensures a break-free function for
most appliances. If you have an alternating voltage back at the input AC IN, transfer
system starts up again with-out any break, and the inverter is stopped.
4.7.3 Delayed mode of the Transfer System
The delayed mode of the transfer system is programmed with the slide switch (D) on
front plate under the battery connection.
The COMPACT provides a break-free alternating voltage for the appliance. A quick
transfer switch is not always sensitive nor is it always desired. For example, when the
appliances are operated by a small back-up generator. An overload of a short period
on such a generator, i.e. start of a vacuum cleaner etc., has the effect of decreasing
the voltage for a short time. As in such cases the transfer to the Inverter is not
desired, the transfer system can be programmed with a delay. When the slide switch
"Transfer delay" (D) is in the „On" position, the transfer to the inverter takes place
with a delay of 5 seconds. If the voltage falls below 100Vac, the transfer takes place
without delay! The transfer switching to the Inverter takes place without any break.
4.8

The Multifunctional Contact

In the COMPACT there is a built-in programmable power relay. The potential-free
change-over contact (NO – NC) of this power relay is connected to the screw
terminal AUX CONTACT.
Maximum Contact load: 230Vac / 12Vdc / 24Vdc / 16A !
> 36Vdc / 3A !
With the Push Button 21 „AUXILIARY CONTACT" the contact can be manually
switched on or off independently from programming and from the operating situation.
The LED 5 "Contact active" shows the status of the contact. The drawing up the
screw terminal "AUX CONTACT" is the inactive position mode, LED 5 "Contact
active" off.
The switching on and off of this contact can be freely programmed for every
operating situation of the COMPACT witch situation is indicated with a LED. There is
no limitation to its application and it is left to your wishes as to where and how you
would like to use it. The example and the setting of this contact are explained in
chapter 5.4.
COMPACT V6.4
20/56