CARACTERISTIQUES TECHNIQUES
TECHNICAL DATA
TECHNISCHE DATEN
APPLICATION BASSE TEMPERATURE
ECARTEMENT D'AILETTES : 4,4 mm
MODELE
MODEL
MODELL
Ventilateur / Câblage
Fan / Wiring
Ventilator / Verdrahtung
Puissance frigorifique (1)
Cooling capacity (1)
Kühlleistung (1)
Débit d'air
Airflow
Volumenstrom
Projection d'air standard (2)
Standard air throw (2)
Standard Wurfweite (2)
Niveau pression sonore
Sound pressure level
Schalldruckpegel
Classe énergétique
Energy Efficiency Class
Energieeffizienzklasse
Connexion entrée (sur distributeur)
Inlet connection (on distributor)
Anschluss Flüssigkeit (am Verteiler)
Connexion sortie
Outlet connection
Anschluss Saugleitung
Surface
Surface
Fläche
Volume du circuit
Circuit volume
Volumen des Kreislaufs
Puissance
Option dégivrage
Power
électrique batterie
Leistung
Optionnal electrical
Intensité 230V/~1/50Hz
coil defrost
Optionale
Current 230V/~1/50Hz
elektrische abtauung
Stromversorgung
230V/~1/50Hz
Longueur
Length
Länge
Poids net à vide
Empty net weight
Netto-Leergewicht
(1) Conditions :
SC3 : Fluide = R404A
Température d'entrée d'air = -18°C
Température d'évaporation = -25°C
Température de liquide = 20°C
Humidité relative = 95%.
(2) La projection d'air indiquée est valable sous la condition
isothermique 20°C et évaporateur collé au plafond.
Les résultats obtenus sur le lieu de l'installation peuvent
être différents par rapport aux valeurs du catalogue, du
fait de la géométrie de la chambre, du chargement de
la chambre, de l'emplacement de l'évaporateur, de la
formation de givre sur l'évaporateur, et de la différence de
température air soufflé-air ambiant.
6
LOW TEMPERATURE APPLICATION
FIN SPACING : 4,4 mm
kW
m³/h
m
3m
dB(A)
m²
dm
3
W
A
L
mm
kg
(1) Conditions:
SC3 : Fluid = R404A
Inlet air temperature = -18°C
Evaporating temperature = -25°C
Liquid temperature = 20°C
Relative humidity = 95%.
(2) The air throw indicated is valid under the condition
isothermal 20°C and cooler under the roof.
The results obtained on the place of the installation can
differ from the values catalog,
due to the geometry of the room, loading
the room, the place of the cooler, the formation of frost
on the cooler, and the difference temperature between
ambient air - blown air.
TIEFKÜHLUNG
LAMELLENABSTAND 4,4 mm
BN 2256
2 x Ø 200
1,29
840
4
46
E
1/2"
5/8"
6,3
1,8
1200
5,2
824
21
(1) Bedingungen:
SC3 : Kältemittel = R404A
Lufteintrittstemperatur = -18 °C
Verdampfungstemperatur = -25 °C
Flüssigkeitstemperatur = 20 °C
Relative Luftfeuchtigkeit : 95 %.
(2) Die angegebene Wurfweite ist gültig bei der
Betriebsbedingung von 20 ° C Raumtemperatur und
Verdampfer unter der Obergrenze.
Die am Einsatzort desVerdampfers erzielten Ergebnisse
können von den Katalogwerten abweichen, bedingt durch
die Geometrie des Raumes, Beschickung des Raumes,
der Montageort des Verdampfers, die Eisbildung von im
wärmetauscherpaket und die Temperaturdifferenz zwischen
der Ansaug- und der Ausblasluft.
BN 2356
3 x Ø 200
1,91
1360
4
48
E
1/2"
5/8"
9,4
2,6
1800
7,8
1154
29