Herunterladen Inhalt Inhalt Diese Seite drucken

Response Of The Output Contact Af For A Fault In The Measurement / Supply Circuit; Mounting - Camille Bauer SIRAX B 811-6 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

10.3 Response of the output signals A1 and A12 for a
fault in the measurement/supply circuit
The response of the output signals A1 and A12 can be
set with the aid of switches 1 and 2 on the DIP switch
S 201 (Fig. 13).
Response of output signals
A1 and A12 for a short or
open-circuit of the measure-
ment / supply circuit
Linear
output signal
Increasing
output signal
Decreasing
output signal
(only with live zero signal)
Fault
Output
linear
behaviour
0 mA
(with output
4...20 mA)
Break
– 5 mA
(with output
0...20 mA)
Approx.
Short-
26 mA
circuit
with output
0/4...20 mA
10.4 Response of the output contact AF for a fault in the
measurement / supply circuit
The response of the fault signalling relay can be set with
the aid of switches 3 and 4 on the DIP switch S 201
(Fig. 13).
Operating sense of
the fault signalling
relay AF in the event
of a fault
Relay energised
Relay de-energised
S201
ON
OFF
1 2 3 4 5 6
J202
Fig. 13. Positions of the DIP switches S 201 and jumpers J 202 to
J 205.
Dip switch S 201
Switch
Switch
1
2
ON
OFF
OFF
OFF
OFF
ON
Output
Output
driving
driving
upscale
downscale
(with
live-zero
Approx.
only)
115%
of full
Approx. 10%
scale end
of full scale
value
end value
e.g. 2 mA
e.g. 23 mA
with output
with output
4...20 mA
0/4...20 mA
or
or
1 V
11.5 V
with output
with output
2...10 V
0/2...10 V
Dip switch S 201
Switch 3
Switch 4
ON
OFF
OFF
ON
J203
1
3
1
J204
J205
1
3
3

11. Mounting

The power pack SIRAX B 811 is plugged onto a backplane
BP 902.
When deciding where to install the power pack
(measuring location), take care that the limits of
the operating temperature are kept:
– 25 and + 55 °C for standard instruments
– 20 and + 55 °C for Ex version!
11.1 Plugging the module into the backplane
Before inserting the SIRAX B 811 into the
backplane, ensure that, ...
...
the backplane wiring is in strict accord-
ance with the wiring diagram of the
module
...
the backplane is coded correctly
according to the section entitled
"Mechanical coding of the backplane".
Read the instructions for the back-
plane.
...
the red coding insert has been removed
from the backplane for SIRAX plug-in
modules with a power supply of
24...60 V DC/AC and that the power
supply is correct for the module.
1. Clip the module base onto the top-hat rail.
2. If the backplane is mounted vertically, turn the quick
release screws on the module to a vertical position,
respectively if it is mounted horizontally, turn the screws
to a horizontal position.
3. Press the quick release screws inwards with the screw-
driver until there is an audible click.
1.
Fig. 14. Plug the module into the base.
2.
3.