Operation

► Check whether the unit operates correctly�
> The LED lights when the switching output is switched�
> The detected distance value is shown in the display�
8.2 Electronic lock
The unit can be locked electronically to prevent unintentional settings� On delivery
the unit is not locked�
Locking
► Make sure that the unit is in the normal operating mode�
► Keep [+] + [-] pressed, until [Loc] is displayed�
> The unit is locked�
Unlocking
► Keep [+] + [-] pressed, until [uLo] is displayed�
> The unit is unlocked�
8.3 Fault indication
Display
[++]
[--]
[nEA]
[FAr]
[ERP]
[SC]
16
Possible cause
Too much light,
e�g� reflective surfaces
Not enough light, no object
Object to be measured outside the
measuring range < 30 mm
Object to be measured outside the
measuring range > 2500 mm
Plausibility (e�g� object too fast)
Short circuit at the switching output
Switching output
[Hno]
[Hnc]
ON
OFF
ON
OFF
unchanged
unchanged
OFF
ON
OFF
ON