Simulation mode
Changeover to simulations mode Press «Sim1»
Changeover to simulation mode:
Press the Sim1 + Sim2 buttons
simultaneously for 2 seconds.
Simulation mode:
Activation of the loop
Activation of the output relay
Alarm output activation
Inductance of loop 1
Inductance of loop 2
Exiting simulation mode
6

Troubleshooting

If an error occurs, operating mode «A» and error display «E» light up alternately and an error code such as E 012 is displayed. The LED changes to
flashing red, the 4 most recent errors are stored and can be interrogated.
Display
E001
Interruption
Error
Loop 1
Briefly pressing the «Data» button shows the last of 4 errors on the display. Another short press switches to the error before that, and so on. When
the button is pressed for the 5th time, the device switches back to automatic mode. If you press the «Data» button for 4 seconds during the query,
all error messages are deleted. The figure shows memory slot 1 in which error 001, Interruption loop 1, has been stored (example).
7
Reset
Reset 1 (recalibration)
Mode
Sim1
The loop(s) is/are recalibrated.
2 Sekunden
8
Most important technical data
Supply voltage /
Power consumption
Loop inductance
Loop connection wiring
Loop resistance
Output relay (loop)
Output relay (alarm)
Dimensions
Housing mounting
Connection type
Protection class
Operating temperature
Storage temperature
Air humidity
9
Declaration of conformity
Manufacturer:
Authorised rep:
Following directives have been observed:
Signee:
Product variant:
10
Contact data
Manufacturer:
Bircher Reglomat AG
Wiesengasse 20
CH-8222 Beringen
www.bircher-reglomat.com
4
Press «Sim2»
button
button
Data
Mode
Sim2
Sim1
2 Sekunden
2 seconds
Data
1
Sim2
Mode
Data
1
Sim1
Sim2
Mode
Data
Sim1
Sim2
Mode
1
Sim1
Mode
2
Sim1
Mode
1
2
Sim1
2 seconds
E002
E011
E012
Interruption
Short circuit
Short circuit
Loop 2
Loop 1
Loop 2
ProLoop2
• 24 ACDC: 24 VAC -20 % to +10%, max. 2 VA
24 VDC -10 % to +20%, max. 1.5 W
• LVAC:
100-240 VAC ± 10%, 50/60 Hz, max. 2.9 VA
max. 20 to 1000 µH,
ideally 80 to 300 µH
At 20-40 µH: max. 100 m at 1.5 mm
At >40 µH: max. 200 m with 1.5 mm
min. twisted 20x/m
< 8 Ohm with connection wire
max. 240 VAC; 2 A / 30 VDC; 1 A; AC-1
max. 40 VACDC; 0.3 A; AC-1
22.5 x 94 x 88 mm (B x H x T)
Direct DIN rail mounting
Plug-in terminals
IP 20
-20°C to +60°C
-40°C to +70°C
<95% non-condensing
Bircher Reglomat AG, Wiesengasse 20, CH-8222 Beringen
Bircher Reglomat GmbH, Robert Bosch Strasse 3, D-71088 Holzgerlingen
RoHS Directive 2011/65/EU, R&TTE-Directive 1999/5/EC until 19.04.2016, RED 2014/53/EU from 20.04.2016
Head of Sales & Marketing Damian Grand / Head of Operations Daniel Nef
ProLooP2 1.24ACDC, ProLoop2 1.A.24ACDC, ProLoop2 1.LVAC, ProLoop2 1.A.LVAC, ProLoop2 2.24ACDC,
ProLoop2 2.A.24ACDC, ProLoop2 2.LVAC, ProLoop2 2.A.LVAC
Press «Sim2»
Press «Sim2»
button
button
1
Mode
1
2
Sim1
1
Mode
2
Sim1
E101
E102
E201/E202 E301
Under -
Over-
Saving
voltage
voltage
error
Mode
Data
Sim1
Sim2
8 Sekunden
2
2
Notes
L0 -
L1 -
No loop activation (time functions are active)
Data
2
Loop activation (time functions are active)
Sim2
- Loop 1
- Loop 2
0 -
0
1 -
Activation of output
Data
0
2
Sim2
Activation of output
- Loop 1
- Loop 2
A0
A1
-Switch off alarm relay
Switch on alarm relay
-
Measurement of the inductance, value in
Measurement of the inductance, value in
Return to function mode
E302
E311
Loop 1
Loop 2
Loop 1
too large
too large
too small
Reset 2 (factory setting)
All values (except the error memory) are reset to the factory
settings (see Table 4.11a). The loop(s) is/are recalibrated.
µH
µH
E312
Loop 2
too small