Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens 7KE6020-1AA00 Handbuch Seite 43

Usb alarm box
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English
EMC tests for emission (type tests)
Standard
Radio interference current on lines
Signal-/data lines only
IEC CISPR 22
Interference field strength
IEC CISPR 22
Mechanical tests, vibration and shock,
stationary use
Vibration
IEC 60068-2-6
Shock
IEC 60068 -2-27
Seismic vibration
IEC 60068-3-3
Mechanical tests, vibration and shock
stress, during transport
Vibration
IEC 60068-2-6
Shock
IEC 60068-2-27
Shock
IEC 60068-2-29
43 / 48
EN 61000-6-3
150 kHz to 30 MHz
Limit class B
30 to 1000 MHz
Limit class B
10 to 200 Hz
2
2 m/s
(0.2 g)
1 Octave/min
20 cycles in 3 orthogonal axes
Semi-sinusoidal, 5 g acceleration, 11 ms duration
3 shocks each along both directions for the 3 axes
Sinusoidal
1 to 8 Hz: +/-3,5 mm amplitude,
8 to 35 Hz: 1 g acceleration (horizontal)
1 Hz to 8 Hz: +/-1.5 mm amplitude, 8 Hz to 35 Hz:
0.5 g acceleration (vertical)
1 Octave/min
1 cycle in 3 orthogonal axes
5 to 200 Hz
+/- 5 mm - below 7 Hz
2
10 m/s
(1 g) – above 7 Hz
1 octave/min
20 cycles in 3 orthogonal axes
Semi-sinusoidal, 15 g acceleration, 11 ms duration
3 shocks each in both directions of the 3 axes
Semi-sinusoidal, 10 g acceleration, 16 ms duration
1000 shocks each in both directions of the 3 axes
E50417-H1074-C337-A1