S202-serie numerische digitalanzeigen mit modbus-rtu-schnittstelle

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Data lines RS485
To achieve the highest possible interference immunity, the data lines of the RS485
have to be terminated on both ends. The required resistors are provided in the unit
and can be connected on the screw terminal strip with a jumper (see block diagram,
terminals ZR, ZT).
The polarization of the data lines must be ensured by means of the master.
For the data lines, you always have to ensure that:
Shielded twisted-pair cables of sufficiently large cross-section are used.
The shielding is connected on both line ends.
For the signal ground (SGD, GND, COM) use a wire pair short-circuited on both
ends in the data cable. The shielding may not be used as the signal ground.
A twisted core pair is used each for Tx+ and Tx- and for Rx+ and Rx-. Non-
observance of this instruction causes the protective function of the twisted-pair
cable to be lost!
Improperly terminated data lines cause faults during data transfer.
Interface parameters
Parity and baud rate are set in menu items 3 and 4.
Adsress
The individual slave address can be set in menu item 9 from 1 to 247.
Data format
The data format for the evaluation of the Modbus data is set by the start address:
Integer modi
ASCII mode
BAL S202 MDB M 1.0
Start address 0000
Start address 0010
Start address 0020
Start address 0030
Start address 0040
: UI16 (16 bit unsigned integer)
h
: SI16 (16 bit signed integer)
h
: UI24 (24 bit unsigned integer)
h
: SI24 (24 bit signed integer)
h
h
31